DATALOGGER (DataLink data recorder) NOT RECORDING
• ACTIVATION: No data is being recorded by the DataLink data recorder.
• UNIT CONTROL: Engine and Electric Operation: Alarm only.
• RESET CONDITION: Alarm may be manually reset using the display mounted keys.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (Refer to Note 1 in
Section, page 7-2.) Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Clear Alarm
a. Clear Active Alarm(s).
b. Check for Active Alarm re-occurrence. If Inactive, download all data & retain. If Active, go to next
step.
2.
Main Microprocessor Defective
a. Download previous data using a Data Transfer USB memory device, or TRU-Tech. Data retrieval
OK.
b. Replace and setup main microprocessor. Refer to
.
NOTE
Specific Configurations may be found on the TransCentral Website (Authorized Carrier Transicold
Dealers only).
00060
DATALOGGER (DataLink data recorder) TIME WRONG
• ACTIVATION: The real time clock in the DataLink data recorder does not contain a valid date.
• UNIT CONTROL: Engine and Electric Operation: Alarm only.
• RESET CONDITION: Auto reset when the DataLink data recorder real time clock is reset, or alarm may
be manually reset by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see
if any active alarm occurs. Continue with the steps below as necessary.
1.
Check Real Time Clock
Check Real Time Clock in the Unit Data, or using TRU-Tech. Must show correct date and time.
Change as needed. Refer to
2.
Reset Microprocessor
a. Place the SROS in the OFF position for 30 seconds and then return it to the START/RUN position.
Microprocessor powers up OK.
b. Check for valid real time clock reading in Unit Data. Valid date and time in memory. Alarm is
cleared automatically.
c. Real Time Clock can not be changed. Proceed to step 3.
3.
Main Microprocessor Defective
a. Download previous data using a Data Transfer USB memory device, or TRU-Tech. Data retrieval
OK.
b. Replace and setup main microprocessor. Refer to
.
Summary of Contents for Vector 8500
Page 23: ...62 11640 1 6 1 3 SAFETY DECALS ...
Page 24: ...1 7 62 11640 62 03958 ...
Page 25: ...62 11640 1 8 ...
Page 26: ...1 9 62 11640 ...
Page 27: ...62 11640 1 10 ...
Page 125: ...62 11640 SECTION 6 MESSAGECENTER PARAGRAPH NUMBER Page 6 1 MESSAGECENTER MESSAGES 6 1 ...
Page 321: ......
Page 322: ......