62-11640
7–12
00019
LOW FUEL SHUTDOWN
NOTE
This is an optional alarm. This alarm will not occur if the Fuel Level Sensor Configuration is NO.
• ACTIVATION: The fuel level is 10% or less for more than 60 seconds AND Alarm 000126 - “Check Fuel
Sensor Circuit” is not active.
• UNIT CONTROL: Engine Operation: Engine and unit shutdown and alarm.
Electric Operation: Alarm condition only.
• RESET CONDITION: Auto reset when fuel level is above 12% for more than 1 minute, or alarm may be
manually reset using the display mounted keys or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check For Low Fuel
Level
Check level in the tank. Add fuel as needed.
2.
Check Low Fuel Level
Sensor
Refer to procedure for alarm
00126 CHECK FUEL SENSOR CIRCUIT
. Alarm condition must be cor-
rected and the alarm cleared to continue.
00020
MAXIMUM COMPRESSOR ALARMS
• ACTIVATION: This option must be installed and alarm must be enabled by configuring the Compressor
Alarm Shutdown to YES. Alarms 00013, 00017, 00018, 00027, or 00028 individually occur 3 times within
the last 2 hours.
• UNIT CONTROL: Engine Operation: Engine and unit shutdown and alarm.
Electric Operation: Refrigeration system shutdown and alarm with PSCON still ener-
gized.
• RESET CONDITION: Clear the alarm from inactive alarm list. This alarm and the alarm(s) that caused it
can not be reset by turning switch OFF and then ON again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see
if any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Determine Which Alarm Activated This
Alarm
a. Check active alarm list for Alarm 00013, 00017, 00018, 00027, or 00028. One or more of these
alarms will be present.
b. Follow the troubleshooting steps for the alarm(s) found, and correct the alarm condition. All alarm
conditions must be corrected.
2.
Reset
Alarm
Clear all inactive alarms. Refer to
. All alarms must be cleared to start unit.
Summary of Contents for Vector 8500
Page 23: ...62 11640 1 6 1 3 SAFETY DECALS ...
Page 24: ...1 7 62 11640 62 03958 ...
Page 25: ...62 11640 1 8 ...
Page 26: ...1 9 62 11640 ...
Page 27: ...62 11640 1 10 ...
Page 125: ...62 11640 SECTION 6 MESSAGECENTER PARAGRAPH NUMBER Page 6 1 MESSAGECENTER MESSAGES 6 1 ...
Page 321: ......
Page 322: ......