62-11640
7–46
00095
CHECK CDCON1 COIL
• ACTIVATION: Condenser fan motor contactor (CDCON) circuit is shorted or open.
• UNIT CONTROL: Engine and Electric Operation: Alarm only.
• RESET CONDITION: Auto Reset or alarm may be manually reset via keypad or by turning the unit off,
then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check CDCON
a. Inspect contactor coil and connector. Verify there is no damage to coil, and no damage, moisture,
or corrosion in connector.
b. Check contactor coil resistance. Refer to
for contactor coil resistance values. Cannot
be opened (infinite ohms), shorted (Zero Ohms) or shorted to ground.
2.
Check CDCON Using Component Test Mode
a. Use Component Test Mode to energize CDCON. (Refer to
) Verify Current Draw on
Component Test Mode Screen. Refer to
for correct electrical values.
b. Check coil voltage between A1 and A2. Verify 12 VDC between A1 & A2.
c. Check resistance at contacts. Verify contacts are closed at L1
−
T1, L2
−
T2, L3
−
T3. 3 Check
CDCON Wiring Inspect harness & control box connector pins & terminals. (See wiring schematic
) Verify there is no physical damage to harness, and no damage, moisture, or corro-
sion in connectors.
3.
Check CDCON Wiring
Inspect harness & control box connector pins & terminals. (See wiring schematic
) Ver-
ify there is no physical damage to harness, and no damage, moisture, or corrosion in connectors.
Summary of Contents for Vector 8500
Page 23: ...62 11640 1 6 1 3 SAFETY DECALS ...
Page 24: ...1 7 62 11640 62 03958 ...
Page 25: ...62 11640 1 8 ...
Page 26: ...1 9 62 11640 ...
Page 27: ...62 11640 1 10 ...
Page 125: ...62 11640 SECTION 6 MESSAGECENTER PARAGRAPH NUMBER Page 6 1 MESSAGECENTER MESSAGES 6 1 ...
Page 321: ......
Page 322: ......