Installation and Operation Manual
X-DPT-DeviceNet-SLA5800-SLAMf-Series-RevB-PC-eng
Part Number: 541B200AAG
March, 2015
74
Section 5 - Detailed Configuration
Brooks DeviceNet PCs
Table 5-76 S-Single Stage Controller Instance 1 Attributes
Attrib
ID Name
Data
Type
Access
Rule NV
Description
Notes
3
Data Type
USINT
Cond.
NV
Defines the Data Type of
Setpoint[6] and other attributes in
this object.
See ‘Note: Data Type’
below
Default = INT
4
Data Units
ENGUNITS
Cond.
NV
Defines the Engineering Units
context of Setpoint[6] and other
attributes in this object
See ‘Note: Data Units’
below
Default = Counts
6 Setpoint
Specified
by Attrib.
3 & 4
Set
V
The sensor value that the device
will maintain at steady state
condition.
10
Status
BYTE
Get
V
Alarm and Warning status for the
S-Single Stage Controller Object
See ‘Note: Status’
below
11
Alarm Enable
BOOL
Set
NV
Enables setting of the Alarm bit
See ‘Note: Alarms’
below
0 = disabled [default]
1 = enabled
12
Warning Enable
BOOL
Set
NV
Enables setting of the Warning bit
See ‘Note: Warnings’
below
0 = disabled [default]
1 = enabled
13 Alarm
Settling
Time
UINT
Set
NV
Number of milliseconds allowed for
the control-loop to settle to within
the error band
See ‘Note: Alarms’
below
Default = 0
14 Alarm
Error
Band
Specified
by Attrib.
3 & 4
Set
NV The maximum deviation band by
which Setpoint must equal the
Process Variable before an alarm
is enunciated.
See ‘Note: Alarms’
below
Default = 0
15 Warning
Settling
Time
UINT
Set
NV
Number of milliseconds allowed for
the control-loop to settle to within
the error band
See ‘Note: Warnings’
below
Default = 0
16 Warning
Error
Band
Specified
by Attrib.
3 & 4
Set
NV The maximum deviation band by
which Setpoint must equal the
Process Variable before an
warning is enunciated.
See ‘Note: Warnings’
below
Default = 0