Section 3 - Quick Start
Brooks DeviceNet PCs
4 Common
Warnings
5
Device Profile Specific Warnings
6
Manufacturer Specific Warnings
7
1 (Extended Reporting Enabled)
A 16-bit signed integer (-32768 to 32767) to represent Pressure in data units
of counts
1
.
The numeric range definitions for Pressure are:
Table 3-3 **Pressure
Counts
Range
< 0
0 - 24576
24577 - 27033
27034 - 32767
Pressure Less
than
calibrated
zero
0% to 100%
of Full Scale
100+% to 110%
of Full Scale
110+% to 133% of
Full Scale
A 16-bit signed integer (-32768 to 32767) to represent the setpoint value in
data units of counts
1
.
The numeric range definitions for Setpoint are:
Table 3-4 ***Setpoint
Counts
Range
< 0
0 – 24576
24577 -27033
27034 - 32767
Setpoint
Not Valid. The minimum
value for setpoint will be
clamped to 0% of Full
Scale
0% to 100%of
Full Scale
100+% to
110% of Full
Scale
Not Valid. The
maximum value for
setpoint will be clamped
to 110% of Full Scale
1
The Data Units Counts is a dimensionless unit that defines a range of numbers to represent a quantity. See Configuration Section for more
information on Data Units counts.
1
The Data Units Counts is a dimensionless unit that defines a range of numbers to represent a quantity. See Configuration Section for more
information on Data Units counts.