Section 5 - Detailed Configuration
Brooks DeviceNet PCs
5.7.1.3. Note: Status
The following table defines the bits in this status byte. The value of 1 = Set
and 0 = Cleared.
Table 5-61 Status
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0 0 0 0
Low
Pressure
Warning
High
Pressure
Warning
Low
Pressure
Alarm
High
Pressure
Alarm
5.7.1.4. Note: Full Scale
The value of this attribute will depend upon the values configured for
attributes 4 and 35. The following table will describe the behavior of this
attribute.
Table 5-62 Full Scale
Data Units
Full Scale Definition
Counts
Default = 24576 for Full Scale[10]. This allows for an overshoot indication of 133% of the calibrated
full scale (e.g. 32767 = 133%). To change this, utilize the Set Full Scale Counts service to set the
desired 100% full scale. A good formula to use is:
Full Scale Counts = (100% / Desired Percent Overshoot) X 32767
Percent
The value will always be 100.
Any Pressure
Engineering Unit
Full Scale[10] will be determined by using a full scale value contained in the Pressure Applications
set of data. This value will be converted to the configured Data Unit[4]. Example: If Instance 1 of an
Pressure Application has a full scale value of 20 torr, and the desired Data Units[4] in the Sensor
Object is milli-torr, the value of Full Scale[10] will be 20000.