Installation and Operation Manual
X-DPT-DeviceNet-SLA5800-SLAMf-Series-RevB-PC-eng
Part Number: 541B200AAG
March, 2015
65
Section 5 - Detailed Configuration
Brooks DeviceNet PCs
5.7.1.8. Note: Warnings
Enable the reporting of Warnings for the S-Analog Sensor object via Warning
Enable[9] attribute. When Pressure[6] exceeds the limits set by Warning Trip
Point High[21] or Warning Trip Point Low[22] a corresponding bit from the
Status[7] attribute is set, see Status above.
The attribute Warning Settling Time[24] sets the interval of a timer that
masks the reporting of warnings. Once the timer expires if a warning
condition still exists the warning is reported.
If warnings are enabled in the S-Device Supervisor Object the actuator
warnings are reported via the Exception Status [12] and corresponding
Exception Detail Warning[14] of the S-Device Supervisor Object.
5.7.2. Services
Table 5-64 S-Analog Sensor Instance 0 Services
Service
Code Service
Name
Service Description
Details
0x0E
Get Attribute Single
Returns the contents of the specified attribute
Appendix E: Get Attribute Single
Table 5-65 S-Analog Sensor Instance 1 Services
Service
Code Service
Name
Service Description
Details
0x0E
Get Attribute Single
Returns the contents of the specified attribute
Appendix E: Get Attribute Single
0x10
Set Attribute Single
Sets the contents of the specified attribute with
the value passed with this service
Appendix E: Set Attribute Single
0x4B
Zero Adjust
Indicates to the device that the current
Pressure Sensor value is zero.
0x32
Set Full Scale Counts
Defines the Counts value that represents
100% of the calibration full scale
This only affects the way the value
of Pressure[6) is reported in relation
]to the Full Scale[10] when the
Units[4] is set to Counts.