![Brooks SLA5800 Series Supplemental Manual Download Page 80](http://html1.mh-extra.com/html/brooks/sla5800-series/sla5800-series_supplemental-manual_2818721080.webp)
Installation and Operation Manual
X-DPT-DeviceNet-SLA5800-SLAMf-Series-RevB-PC-eng
Part Number: 541B200AAG
March, 2015
66
Section 5 - Detailed Configuration
Brooks DeviceNet PCs
5.7.2.1. Service Details
5.7.2.2. Set Full Scale Counts
Table 5-66 Set Full-Scale Counts Service Arguments
Parameter
Name
Data
Type Required
Parameter
Value
Semantics
Full Scale
Counts
INT
Y
-32768 to 32767
The Counts value that defines 100% of the full scale. The
value that is passed here in this argument will be
reported in attribute Full Scale[10].
Table 5-67 Set Full-Scale Counts Service Response
Parameter Name
Data Type
Required Value
Parameter
Description
NO SUCCESS RESPONSE DATA
5.8. S-Analog Actuator Object [0x32]
The S-Analog Actuator is responsible for management of the actuator device
controlling the process.
5.8.1. Attributes
Table 5-68 S-Analog Actuator Instance 0 Attributes
Attrib
ID Name
Data
Type
Access
Rule NV
Description
Notes
1
Revision
UINT
Get
NV
Revision of the S-Analog
Actuator object class
definition upon which the
implementation is based.
If updates require an increase
in this value, then the value of
this attribute increases by 1.
Range 1– 65535