Installation and Operation Manual
X-DPT-DeviceNet-SLA5800-SLAMf-Series-RevB-PC-eng
Part Number: 541B200AAG
March, 2015
67
Section 5 - Detailed Configuration
Brooks DeviceNet PCs
Table 5-69 S-Analog Actuator Instance 1 Attributes
Attrib
ID Name Data
Type
Access
Rule NV
Description
Notes
3
Data Type
USINT
Cond.
NV
Defines the Data Type of Value[6]
and other attributes in this object.
See Note ‘Data Type’
below
Default = INT
4
Data Units
ENGUNITS
Cond.
NV
Defines the Engineering Units
context of Value[6] and other
attributes in this object.
See Note ‘Data Units’
below
Default = Counts
5
Override
USINT
Set
V
Specifies a direct override of the
physical actuator
See Note ‘Override’
below
6 Value
Specified
by
Attrib. 3 & 4
Get
V
The value of the analog output signal
used to drive the physical actuator
See Note ‘Value’ below
7
Status
BYTE
Get
V
Alarm and Warning status for the S-
Analog Actuator Object
See Note ‘Status’ below
8 Alarm
Enable
BOOL
Set
NV
Enables setting of the Alarm bit
See Note ‘Alarms’
below
0 = disabled [default]
1 = enabled
9 Warning
Enable
BOOL
Set
NV
Enables setting of the Warning bit
See Note ‘Warnings’
below
0 = disabled [default]
1 = enabled
15 Alarm
Trip
Point High
Specified by
Attrib. 3 & 4
Set
NV
Determines the Value[6] above which
an Alarm condition will occur.
See Note ‘Alarms’
below
[default] = Maximum
value for its data type
16 Alarm
Trip
Point Low
Specified by
Attrib. 3 & 4
Set
NV
Determines the Value[6] below which
an Alarm condition will occur.
See Note ‘Alarms’
below
[default] = Minimum
value for its data type
18 Warning
Trip Point
High
Specified by
Attrib. 3 & 4
Set
NV
Determines the Value[6] above which
a warning condition will occur.
See Note ‘Warnings’
below
[default] = Maximum
value for its data type