![Brooks SLA5800 Series Supplemental Manual Download Page 35](http://html1.mh-extra.com/html/brooks/sla5800-series/sla5800-series_supplemental-manual_2818721035.webp)
Installation and Operation Manual
X-DPT-DeviceNet-SLA5800-SLAMf-Series-RevB-PC-eng
Part Number: 541B200AAG
March, 2015
21
Section 4 - Configuration
Brooks DeviceNet PCs
4.1.7. Pressure Sensor Group
Table 4-4 Supported Pressure Sensor Parameters
EDS Parameter
Values
Description
EPATH
Pressure Sensor
Data Type
1,
2,
3
Appendix B - Data Type
Definitions
The data type associated with
reporting Pressure
[0x31-1-3]
Pressure Sensor
Data Units
2
See “Pressure Units Table” in
Appendix C -Data Units
The engineering units associated
with reporting Pressure
[0x31-1-4]
Pressure Sensor
Safe State
See Note: Pressure Sensor
Safe State below
Configures the behavior of the
Pressure sensor when the device is
in Safe Mode
[0x31-1-25]
Pressure
Application
From one up to the number
of applications in the device
Sets the calibration values used by
the sensor to linearize the Pressure
sensor
[0x31-1-35]
4.1.8. Pressure Sensor Safe State Values
The following table outlines valid safe states for the Pressure Sensor.
Table 4-5 Pressure Sensor Safe State Values
Value State
Description
0
Zero (default)
The sensor value will be zero
1
Full Scale
The sensor value will equal Full Scale
2
Hold Last Value
The sensor value will hold to the most recent
sensor reading just prior to entering the safe state
3
Use Safe Value
The sensor value will equal Safe Value attribute of
the S-Analog Sensor Object
4 Continue
Sensing
The sensor value will continue to update normally
as if in the Executing State
100
Track
The sensor value will continue to update normally
as if in the Executing State
1
This parameter is only configurable when the device is in the Idle State (i.e. when the device is not being actively scanned/polled).
2
This parameter will automatically be set based upon the inferred data type of the selected Assembly used for I/O (i.e. if the Assembly that is
selected to report pressure is INT, then this attribute will be automatically set to INT once I/O data exchange begins).
3
The device only supports values INT and REAL. All others will be rejected.