Section 3 - Quick Start
Brooks DeviceNet PCs
Figure 3-4 View Showing Top of PC Can.
When power is applied to the device, each LED will flash red, then green a
minimum of one time. This is a LED verification test. If this does not occur, go
to the Troubleshooting section.
Next the MOD LED (“Module” Status) will then begin to flash red/green
indicating that the device is self-testing. When all internal tests have passed,
approximately 20 to 30 seconds depending on device type, the MOD LED
will turn solid green. If this does not occur, go to the Troubleshooting section.
The NET LED (“Network” Status) will remain off until another node is
connected to the network and completes a Duplicate MAC ID check. This
implies that under normal operating conditions after the initial NET LED
power on sequence has completed the lonely node will never turn on its NET
LED.
Once the device is connected to a network of devices the NET LED
(“Network” Status) should flash green, indicating that the device MAC ID and
Baud Rate are configured properly and the device recognizes the network. It
is now capable of establishing “connections.” Proceed to Step 7.
If the NET LED is solid green, an active connection has now been
established to the device. Proceed to Step 7.
If the NET LED is indicating any other status than those described above,
consult Appendix D for LED flash codes or go to the Troubleshooting section.