Brooks DeviceNet PCs
7.4. Appendix D - LED Flash Codes
The following tables assume power has been applied to the network and the
device has been properly connected to the network.
Table 7-22 NET LED Flash Codes
Flash Code
Description
Off
The device is the only node on the network
Flashing Green
Baud Rate and MAC ID are configured correctly. The device
recognizes the network but no connection has been made to the
device
Solid Green
A Connection has been established to the device
Flashing Red
An I/O Connection to the device has timed out
Solid Red
The Baud Rate Switch is set to a different baud rate than the
network
OR
The MAC ID of the device is identical to another node on the
network
OR
The device has gone Bus Off, indicating network communication
errors.
Table 7-23 MOD LED Flash Codes
Flash Code
Description
Flashing Red-Green
The device is in the Self-Test mode
Solid Green
All self-tests have passed. No faults have been detected
Flashing Red
A recoverable fault has been detected or the device has been
commanded into the Abort state
Solid Red
An unrecoverable fault has occurred