Installation and Operation Manual
X-DPT-DeviceNet-SLA5800-SLAMf-Series-RevB-PC-eng
Part Number: 541B200AAG
March, 2015
48
Section 5 - Detailed Configuration
Brooks DeviceNet PCs
Table 5-32 Instance 2 - M/S Polled I/O Connection Attributes
Attrib
ID Name
Data
Type
Access
Rule Description
Notes
1 State
USINT
Get
State
of
Object
Note: ‘State’ below
Default: 1 = Configuring State
2
Instance Type
USINT
Get
Indicates type of Connection
Default: 1 = I/O Connection
3 Transport
Class
& Trigger
USINT Set
1
Defines behavior of Connection
Note: ‘Transport Class & Trigger’
below
Default: 0x82
4 Produced
Connection ID
UINT
Get
Placed in CAN Identifier Field
when the Connection transmits
5 Consume
Connection ID
UINT
Get
CAN Identifier Field value that
denotes message to be
received
6 Initial
Comm
Characteristics
BYTE
Get
Defines the Message Group(s)
across which productions and
consumptions associated with
this Connection occur
Note: ‘Initial Comm
Characteristics’ below
Default: 0x01
7 Produced
Connection Size
UINT Set
1
Maximum number of bytes
transmitted across this
Connection
Defined by the size of the
Application Data object pointed to
by Produce Connection Path
attribute
8 Consumed
Connection Size
UINT
Get
Maximum number of bytes
received across this
Connection
Defined by the size of the
Application Data object pointed to
by Produce Connection Path
attribute
9 Expected
Packet
Rate (EPR)
UINT Set
Defines
timing
associated
with
this Connection
Must be configured. Once this
value is set, the Polled I/O
Connection transitions to the
Established State
12 Watchdog
Timeout Action
USINT
Set
Specifies how the Connection
will handle inactivity/watchdog
timeouts
Note: ‘Watchdog Timeout Action’
below
Default: 0 = Timed Out Stat
13 Produce
Connection Path
Length
UINT
Get
Number of bytes in the
Produced Connection Path
attribute
Default: 6
14 Produce
Connection Path
EPATH Set
1
Specifies the application object
data to be produced by this
Connection
This attribute is settable only in
the Configuring State
Default: As defined by Attribute
100 in the M/S Explicit
Connection instance.
1
Settable while the connection is in the Configuring State.