Section 5 - Detailed Configuration
Brooks DeviceNet PCs
Attrib
ID Name
Data
Type
Access
Rule Description
Notes
15 Consume
Connection Path
Length
UINT
Get
Number of bytes in the
Consume Connection Path
attribute
Default: 6
16 Consume
Connection Path
EPATH Set
1
Specifies the application object
to receive data by this
Connection
This attribute is settable only in
the Configuring State
Default: As defined by Attribute
101 in the M/S Explicit
Connection instance.
5.5.2.3. Note: State
Table 5-33 Rules Governing Master/Slave Connections [0x5]
Value State
Description
0
Non-Existent
The Connection has not yet been instantiated
1
Configuring
The Connection has been instantiated, but not properly configured. Upon completion
of configuration the Apply service must be sent to the Connection
2 Waiting
for
Connection ID
The Connection is waiting exclusively for the Produce or Consume Connection ID’s to
be set
3
Established
The Connection has been properly configured and applied
4
Timed Out
The Inactivity/Watchdog has timed out and may have transitioned to this state if the
Watchdog Timeout Action attribute has been configured to do so. See Attribute 12.
5
Deferred Delete
If the Connection Object is of Explicit Message Connection type (see Attribute 2) and
the Inactivity/Watchdog has timed out, the Connection may transition to this state if the
Watchdog Timeout Action attribute has been configured to do so. See Attribute 12.