12/16
Operating Instructions ACU
187
The current application warning mask can be read via parameter
Actual Appl. Warning Mask
627
.
The Operation Modes of parameter
Create Appl. Warning Mask
626
are encoded in the
Actual
Appl. Warning Mask
627
. The code is calculated by hexadecimal addition of the individual
operation modes and the corresponding abbreviation
Warning code
Create Appl. Warning Mask 626
A 003F
-
2 - Activate all warnings
A 0001 BELT
10 - Warning V-belt
A 0002 SW-LIM CW
11 - Warning pos. SW limit switch
A 0004 SW-LIM CCW
12 - Warning neg. SW limit switch
A 0008 HW-LIM CW
13 - Warning pos. HW limit switch
A 0010 HW-LIM CCW 14 - Warning neg. HW limit switch
A 0020 CONT
15 - Warning position controller
A 0040 Enc
16 - Warning Encoder
A 0080 User 1
17 - User Warnig 1
A 0100 User 2
18 - User Warnig 2
Output signals
The output of a warning is signaled.
215 - Warning
mask,
application
1)
Output of warning activated in
Create Appl. Warning Mask
626.
27 -
2)
1)
For linking to frequency inverter functions
2)
For output via a digital output.
Parameter
Application Warnings
273
displays the application warning regardless of
the warning mask created. In the error environment,
Application Warning Status
367
displays the current warnings of the positioning functions.
16.4
Digital Inputs
The assignment of the control signals to the available software functions can be adapted to the
application in question. Depending on the
Configuration
30
selected, the default assignment or
selection of the operation mode differ. In addition to the available digital control inputs, further
internal logic signals are available as sources.
Each of the individual software functions is assigned to the various signal sources via
parameterizable inputs. This enables a flexible use of the digital control signals.
Digital Inputs
Function
6 -
On
Signal input is switched on.
7 -
off
Signal input is switched off.
13 -
Technology Controller
Start
Start command technology controller (configuration 111, 211 or
411)
70 - FI release
1)
Signal at digital inputs S1IND/STOA (X210A.3) and S7IND/STOB
(X210B.2).
Safety function STO - “Safe Torque Off” is linked permanently.
71 - S2IND
Signal at digital input S2IND (X210A.4) or remote operation via
communication interface.
72 - S3IND
Signal at digital input S3IND (X210A.5) or remote operation via
communication interface.
73 - S4IND
Signal at digital input S4IND (X210A.6) or remote operation via
communication interface.