Operating Instructions ACU
173
16.2
Multifunction Output MFO1
Multifunction output MFO1 can either be configured as a digital, analog or a repetition frequency
output. Depending on the selected
Operation Mode
550
for the multifunction output, a link to
various functions of the software is possible. The operation modes not used are deactivated
internally.
Operation Mode 550
Function
0 - off
Output has the logic signal LOW
1 - Digital
Digital output, 0 ... 24 V
2 - Analog
Analog output, 0 ... 24 V
3 - Repetition frequency
Repetition frequency output, 0 ... 24 V, f
max
= 150 kHz
16.2.1
Analog Output MFO1A
By default, the multifunction output MFO1 is configured for the output of a pulse width modulated
output signal with a maximum voltage of DC 24V.
The selected configuration determines which actual values can be selected for parameter
Analog
Operation
553
of Multifunction output 1.
Analog Operation 553
Function
0 - off
Analog operation MFO1 is switched off.
1 - Abs. Fs
Abs. value of the Stator Frequency
0,00 Hz ...
Maximum Frequency
419
.
2 - Abs. Fs betw.
fmin/fmax
Abs. value of the Stator Frequency
Minimum Frequency 418 ...
Maximum Frequency
419
.
3 - Abs. Speed Sensor 1
Abs. value of speed sensor signal 1,
0,00 Hz ...
Maximum Frequency
419
.
7 - Abs. actual frequency
Abs. value of act. frequency,
0,00 Hz ...
Maximum Frequency
419
.
20 - Abs. Iactive
Abs. value of current effective current I
WIRK
,
0.0 A ... Inverter rated current.
21 - Abs. Isd
Abs. value of flux-forming current component,
0.0 A ... Inverter rated current.
22 - Abs. Isq
Abs. value of torque-forming current component,
0.0 A ... Inverter rated current.
30 - Abs. Pactive
Abs. value of current active power P
WIRK
,
0.0 kW ...
Rated Mech. Power
376
.
31 - Abs. M
Abs. value of calculated torque M,
0.0 Nm ... rated torque.
32 - Abs. inside temperature Abs. value of measured inside temperature,
0 °C ... 100 °C
33 -
Abs. Heat Sink
Temperature
Abs. value of measured heat sink temperature,
0 °C ... 100 °C
40 - Abs. value analog input
MFI1A
Abs. signal value at analog input MFI1A,
0.0 V ... 10.0 V.
50 - Abs. I
Abs. current value of measured output currents,
0.0 A ... Inverter rated current.
51 - DC-Link Voltage
DC-Link Voltage U
d
,
0.0 V ... 1000.0 V.
52 - U
Output voltage U,
0.0 V ... 1000.0 V.
53 - Volume Flow
Abs. value of calculated volume flow
0.0 m
3
/h ...
Nominal Volumetric Flow
397
.