12/16
Operating Instructions ACU
175
16.2.2.1
Scaling
The repetition frequency mode for the multifunction output corresponds to the emulation of an
incremental sensor. Parameter
Division Marks
556
must be set according to the frequency to be
output. The minimum frequency of Repetition Freq. Operation is 30 Hz. Smaller values will be output
as 0 Hz.
The pulse-pause ratio is not 1:1. For this reason, Repetition Freq. Operation should only be
evaluated with the rising or falling edge in the evaluation device.
Parameter
Setting
No.
Description
Min.
Max.
Factory setting
556 Division Marks
30
8192
1024
The frequency limit of f
max
=150 kHz must not be exceeded in the calculation of parameter
Division
Marks
556
.
value
Frequency
Hz
150000
S
max
16.3
Digital Outputs
Op. Mode Digital Output 1
530
and the relay output with parameter
Op. Mode Digital Output 3
532
link the digital outputs to various functions. The selection of the functions depends on the
parameterized configuration. When multifunction output MFO1 is to be used as a digital output, an
Operation Mode
550
must be selected and linked via parameter
Digital Operation
554
.
Operation mode 530, 532,
554
Function
0 - off
Digital output is switched off
1 - Ready or Standby Signal
Frequency inverter is initialized and on stand-by or in operation
2 - Run Signal
Signal enable STO (S1IND/STOA and S7IND/STOB) and a start
command are present, output frequency available.
3 - Error Signal
Message is displayed via parameter Current Error 259 and
Warnings
269
.
4 - Setting Frequency
The Stator Frequency
210
is higher than the parameterized
Setting Frequency
510
.
5 - Reference frequency
reached
The Actual Frequency
241
of the drive has reached the Internal
Reference Frequency
228
.
6 -
Reference percentage
reached
The Actual Percentage Value
230
has reached the Reference
Percentage Value
229
.
7 - Ixt warning
The Warning Limit Short Term Ixt
405
or Warning Limit Long
Term Ixt
406
were reached.
8 - Warning Heat Sink
Temperature
Max. heat sink temperature T
K
of 80 °C minus Warning Limit
Heat Sink Temp.
407
reached.
9 - Inside temperature warning
Max. Inside Temperature T
i
of 65 °C minus Warning
Limit
Inside Temp.
408
reached.
10 - Motor temperature warning Waring behavior as per configured Motor Temp. Operation Mode
570
at max. motor temperature T
PTC .
11 - General warning
Message is displayed via parameter Warnings
269
.
12 - Warning overtemperature
The selected Warning Limit Heat Sink Temp.
407
, Warning Limit
Inside Temp.
408
or maximum motor temperature were
exceeded.
13 - Mains failure
Failure of the mains voltage and power regulation active
according to Operation Mode
670
for the voltage controller.
14 - Warning motor circuit
breaker
Parameterized Operation Mode
571
for motor circuit breaker
was triggered.