Operating Instructions ACU
12/16
Configuration 530, FOC Syn.
N or M Controlled
Configuration 530 extends the functionality of Configuration 510 by functions for
torque-dependent, field-oriented control. The reference torque is represented as a
percentage and it is transmitted into the corresponding operational performance of
the application. Change-over between variable-speed control and torque-dependent
control is done jerk-free during operation.
Configuration 610,
DMR for PMSM
Configuration 610 contains the functions for sensorless field-oriented control of a
synchronous machine with resolver feedback. The separate control of torque and
flux-forming current enables high drive dynamism with a high load moment. The
missing resolver feedback results in slightly lower dynamism and speed quality
compared to Configuration 510.
Configuration
611,
DMR PMSM w. Technology Contr.
Configuration 611 extends the functionality of Configuration 610 by a Technology
Controller. The Technology Controller enables a control based on parameters such
as flow rate, pressure, filling level or speed.
Configuration 630 – DMR PMSM N or M Controlled
Configuration 630 extends the functionality of the sensorless field-oriented control of
Configuration 610 by a Torque Controller. The reference torque is represented as a
percentage and it is transmitted into the corresponding operational performance of
the application. Change-over between variable-speed control and torque-dependent
control is done jerk-free during operation.
9.2.2
Data Set
The data set change-over function enables the selection of one of four data sets for
storing parameter settings.
If data set 0 is selected (factory setting), the parameter values saved in data set 0
are copied to data sets 1 through 4. In this way, all values determined during the
guided commissioning procedure are saved in all data sets. In the factory settings,
the frequency inverter uses data set 1 as the active data set. (For information on
data set change-over via logic signals, refer to the chapter 16.4.7 "Switch data set")
For example, if data set 2 is selected for guided commissioning ("SETUP"), all values
which were determined or entered are saved in this data set. The other data sets
will still contain the default values. For the operation of the frequency inverter, data
set 2 must be selected as the active data set in this case.
Data Set Setup
dS
Function
0
All data sets (DS0)
1
Data set 1 (DS1)
2
Data set 2 (DS2)
3
Data set 3 (DS3)
4
Data set 4 (DS4)