106
Operating Instructions ACU
12/16
After completion of the parameter identification, warning messages may be displayed. Depending on
the warning message code, the following instructions should be followed and the measures indicated
should be taken.
9.2.7
Status messages during commissioning (SS…)
The following status messages are possible when Setup is run:
Status message
Meaning
SS000 OK
Auto set-up routine has been carried out.
SS001 PC Phase 1
The plausibility check (PC) of the motor data is active.
SS002 PC Phase 2
The calculation of dependent parameters is active.
SS003 STO
The parameter identification requires release on digital input
STOA and STOB.
SS004 Parameter
Identification
The rated motor values are checked by the parameter
identification feature.
SS010 Setup already active
The setup routine via the control panel is being carried out.
SS030 No Release
The parameter identification demands the controller release on
digital input STOA and STOB.
SS031 Error – check P. 259
Error during the auto set-up routine. Check value of
Current
Error
259.
SS032 Warning
Phase
Asymmetry
The parameter identification feature diagnosed an unbalance
during the measurements in the three motor phases.
SS099 Setup not carried out
yet.
Self-setup has not yet been carried out.
9.2.8
Warnings during commissioning (SA…)
Warning messages
Code
Measures / Remedy
SA000 No warning message present. This message can be read out via an optional
communication board.
SA001
The value of the parameter
Rated Voltage
370
is out of the rated voltage range of the
frequency inverter. The maximum reference voltage is indicated on the nameplate of the
frequency inverter.
SA002
For a three-phase motor, the calculated efficiency is in the limit range. Check the values
entered for parameters
Rated Voltage
370
,
Rated Current
371
and
Rated Mech. Power
376
.
SA003
The value entered for parameter
Rated Cosinus Phi
374
is outside of normal range (0.6 to
0.95). Check the value.
SA004
For three-phase motor, the calculated slip is in the limit range.
Check the values for parameters
Rated Speed
372
and
Rated Frequency
375
.
SA011 Current Controller non typical value; also see Chapter 18.5.1.
SA012 Current Controller non typical value with 2kHz; also see Chapter 18.5.1.
SA014 Current Controller non typical value with 4 kHz; also see Chapter 18.5.1.
SA018 Current Controller non typical value with 8 kHz; also see Chapter 18.5.1.
SA021 Stator Resistance very high. The following causes are possible:
The motor cable cross-section is not sufficient.
The motor cable is too long.
The motor cable is not connected correctly.
The contacts are not in a proper condition (corrosion).
SA022 Rotor Resistance very high. The following causes are possible:
The motor cable cross-section is not sufficient.
The motor cable is too long.
The motor cable is not connected correctly.
The contacts are not in a proper condition (corrosion).