22.4
Warning Status and Warning Status Application
The current warning is displayed by a message in the warning status and can be used for early
reporting of a critical operational condition. If a warning is present, this is indicated by the flashing red
LED and the display field WARN of the control unit. If several warnings are present, the warning
status is displayed as the sum of the individual warning codes.
The warning masks created through parameters
Create Warning Mask
536
and
Create Appl.
Warning Mask
626
have no influence on the warnings displayed. Via actual value parameters
Warnings
269
,
Application Warnings
273
,
Warning Status
356
(in error environment) and
Application Warning Status
367
(in error environment) all warnings present at the time of the error
are displayed.
Coding of the warning status
AXXXX
ABCDE
Warning key
Warning abbreviation
Meaning of key displayed by parameter
Warning Status
356
:
Key
Warning Status
A 00 00 -
No warning present.
A 00 01 Ixt
Frequency inverter overloaded (A0002 or A0004)
A 00 02 IxtSt
Overload for 60 s relative to the nominal output of the frequency inverter
A 00 04 IxtLt
Short-time overload for 1 s relative to the nominal output of the frequency
inverter.
A 00 08 Tc
Max. heat sink temperature T
K
of 80 °C minus
Warning Limit Heat Sink Temp.
407
reached.
A 00 10 Ti
Max. inside temperature T
i
of 65 °C minus
Warning Limit Inside Temp.
408
reached.
A 00 20 Lim
The controller stated in
Controller Status
275
is limiting the reference figure.
A 00 40 INIT
Frequency inverter is being initialized
A 00 80 PTC
Warning behavior as per configured
Motor Temp. Operation Mode
570
at
max. motor temperature T
Motor
.
A 01 00 Mains
Phase Supervision
576
reports mains phase failure.
A 02 00 PMS
Motor circuit breaker parameterized in
Operation Mode
571
tripped.
A 04 00 Flim
The
Maximum Frequency
419
was exceeded. The frequency limitation is
active.
A 08 00 A1
The input signal MFI1A is lower than 1 V / 2 mA according to the operation
mode for the
Error/Warning Behavior
453
.
A 10 00 A2
The input signal is lower than 1 V / 2 mA according to the operation mode for
the
Error/Warning Behavior
453
.
A 20 00 SYS
A slave on the system bus reports a fault; warning is only relevant with the
EM-SYS option.
A 40 00 UDC
The DC link voltage has reached the type-dependent minimum value.
A 80 00 WARN2 In
Application Warning Status
367
, a warning is present.
Example:
The following warning status is displayed:
A008D Ixt IxtLt Tc PTC
The warning status results from the hexadecimal sum of the warning codes
(0001+0004+0008+0080 = 008D).
The short-term overload (1 s), warning limit heat sink temperature and warning limit
motor temperature warnings are present.