12/16
Operating Instructions ACU
41
5.9
ACU 401 Size 5 (18.5 to 30.0 kW, 400 V)
Type
ACU 401
-27
-29
-31
Size
5
Output, motor side
Recommended motor shaft power
P
kW
18.5
22.0
30.0
Output current
I
A
40.0
45.0
60.0
Long-term overload current (60 s)
I
A
60.0
67.5
90.0
Short-time overload current (1 s)
I
A
80.0
90.0
120.0
Output voltage
U
V
Maximum input voltage, three-phase
Protection
-
-
Short circuit / earth fault proof
Rotary field frequency
f
Hz
0 ... 599, depending on switching frequency
Switching frequency
f
kHz
2, 4, 8
Output, braking resistor
Min. braking resistance
R
Ω
16
Recommended braking resistor
(U
dBC
= 770 V)
R
Ω
26
22
16
Input, mains side
Power supply current
2)
I
A
42.0
50.0
58.0
1)
Mains voltage
U
V
320 ... 528
Mains frequency
f
Hz
45 ... 66
Fuses
I
A
50
63
UL type 600 VAC RK5
I
A
50
60
Mechanical
Dimensions
HxWx
D
mm
250x200x260
Weight approx.
m
kg
8
Ingress protection rating
-
-
IP20 (EN60529)
Connection terminals
A
mm
2
up to 25
Form of assembly
-
-
vertical
Ambient conditions
Energy dissipation (2 kHz switching
frequency)
P
W
445
535
605
Coolant temperature
T
n
°C
0 ... 40 (3K3 DIN IEC 721-3-3)
If required by the customer, the switching frequency may be increased if the output current is reduced at the
same time. Comply with the applicable standards and regulations for this operating point.
Output current
3)
Frequency inverter nominal power
Switching frequency
2 kHz
4 kHz
8 kHz
18.5 kW
40.0 A
40.0 A
40.0 A
22 kW
45.0 A
45.0 A
45.0 A
30 kW
60.0 A
1)
60.0 A
1)
60.0 A
1)
1)
Three-phase connection requires a commutating choke.
2)
Mains current with relative mains impedance ≥ 1% (see Chapter 7 "Electrical installation")
3)
Maximum current in continuous operation