F2AP

EM-5436 Rev.4 

P. 1 / 2

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201   Fax: +81(6)6659-8510   E-mail: [email protected]

DC/FREQUENCY CONVERTER

MODEL

F2AP

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Signal conditioner ...............................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

The actual installation environments such as panel configu-
rations, connected devices and connected wires may affect 
the protection level of this unit when it is integrated in a 
panel system.  The user may have to review the CE require-
ments in regard to the whole system and employ additional 
protective measures to ensure CE conformity.

 

POWER INPUT RATING & OPERATIONAL RANGE

Locate the power input rating marked on the product and 
confirm its operational range as indicated below:
24V DC rating: 24V ±10%, approx. 80mA

 

GENERAL PRECAUTIONS

Before you remove the unit or mount it, turn off the power 
supply and input signal for safety.

 

ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -5 to +55°C     

(23 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

• Be sure that the ventilation slits are not covered with ca-

bles, etc.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

The unit is designed to function as soon as power is sup-
plied, however, a warm up for 30 minutes is required for sat-
isfying complete performance described in the data sheet.

COMPONENT IDENTIFICATION

Body

Zero Adj.

Span Adj.

Connection

Diagram

Specifications

Euro Type 

Terminal Block

INSTALLATION

Set the unit so that its DIN rail adaptor is at the bottom.  
Position the upper hook at the rear side of the unit on the 
DIN rail and push in the lower.
When removing the unit, push down the DIN rail adaptor 
utilizing a minus screwdriver and pull.

DIN Rail

35 mm wide

Spring Loaded

DIN Rail Adaptor

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the con-
nection diagram on the side of the unit.

+

+

OUTPUT

5

6

POWER

7

8

+

INPUT

1

2

• Open Collector

Output Connection 
Examples 

+

5

6

+

• Voltage Pulse

+

5

6

+

SCREWDRIVER (–)

PIN TERMINAL

MULTI-STRAND CABLE

1.25 mm

2

 (.02 in

2

)

PHOENIX CONTACT

AI 1,5-8BK recommended

SOLID CABLE

1.4 mm (.06) dia.

8 mm (.32)

STRIPPED LENGTH

• 

Wiring Procedure for Euro Type Terminal Block