F2AP

EM-5436 Rev.4 

P. 2 / 2

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201   Fax: +81(6)6659-8510   E-mail: [email protected]

CHECKING

1 ) Terminal wiring:  Check that all cables are correctly 

connected according to the connection diagram.

2 ) Power input voltage:  Check voltage across the terminal 

7 – 8 with a multimeter.

3 ) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4 ) Output:  Check that the load resistance meets the de-

scribed specifications shown below. 

Check also that the receiving instrument is able to ac-

cept the waveform as explained in the figure below.

OUTPUT

LOAD REQUIREMENTS

Open collector

30V DC @100mA max.

5V pulse

250Ω min.

• Open Collector

• Voltage Pulse

OFF

ON

20%

80%

1 / f

 Frequency less than 500 Hz at 100% input

          

Duty ratio 20% (See the figure below)

H Level

L Level

20%

80%

1 / f

• Open Collector

• Voltage Pulse

 Frequency greater than 500 Hz at 100% input

          

See the figure and equation below.

H Level

L Level

Pulse Width

OFF

ON

Pulse Width

Pulse Width [millisec.] =

1

2.09 x 100% Frequency [kHz]

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.

 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 30 minutes.

1 ) ZERO:  Apply 5% input and adjust output to 5%.
2 ) SPAN:  Apply 100% input and adjust output to 100%.
3 ) Check ZERO adjustment again with 5% input.
4 ) When ZERO value is changed, repeat the above proce-

dure 1) – 3).

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 30 minutes.  Apply 0%, 5%, 
25%, 50%, 75% and 100% input signal.  Check that the out-
put signal for the respective input signal remains within 
accuracy described in the data sheet.  When the output is 
out of tolerance, recalibrate the unit according to the “AD-
JUSTMENT PROCEDURE” explained earlier.

EXTERNAL DIMENSIONS

  unit: mm (inch)

1 2 3 4

5 6 7 8

107 (4.21)

[1.5 (.06)]

DIN RAIL

35mm wide

22.5 (.89)

75 (2.95)

• When mounting, no extra space is needed between units.