F2AP
EM-5436 Rev.4
P. 2 / 2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
CHECKING
1 ) Terminal wiring: Check that all cables are correctly
connected according to the connection diagram.
2 ) Power input voltage: Check voltage across the terminal
7 – 8 with a multimeter.
3 ) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4 ) Output: Check that the load resistance meets the de-
scribed specifications shown below.
Check also that the receiving instrument is able to ac-
cept the waveform as explained in the figure below.
OUTPUT
LOAD REQUIREMENTS
Open collector
30V DC @100mA max.
5V pulse
250Ω min.
• Open Collector
• Voltage Pulse
OFF
ON
20%
80%
1 / f
■
Frequency less than 500 Hz at 100% input
Duty ratio 20% (See the figure below)
H Level
L Level
20%
80%
1 / f
• Open Collector
• Voltage Pulse
■
Frequency greater than 500 Hz at 100% input
See the figure and equation below.
H Level
L Level
Pulse Width
OFF
ON
Pulse Width
Pulse Width [millisec.] =
1
2.09 x 100% Frequency [kHz]
↓
↓
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■
HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 30 minutes.
1 ) ZERO: Apply 5% input and adjust output to 5%.
2 ) SPAN: Apply 100% input and adjust output to 100%.
3 ) Check ZERO adjustment again with 5% input.
4 ) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■
CALIBRATION
Warm up the unit for at least 30 minutes. Apply 0%, 5%,
25%, 50%, 75% and 100% input signal. Check that the out-
put signal for the respective input signal remains within
accuracy described in the data sheet. When the output is
out of tolerance, recalibrate the unit according to the “AD-
JUSTMENT PROCEDURE” explained earlier.
EXTERNAL DIMENSIONS
unit: mm (inch)
1 2 3 4
5 6 7 8
107 (4.21)
[1.5 (.06)]
DIN RAIL
35mm wide
22.5 (.89)
75 (2.95)
• When mounting, no extra space is needed between units.