9
•
Transmits notifications through GSM 900/1800 cellular communication channels providing
backup operation (the second SIM card).
•
Provides transmitting to five phone numbers with programming the following notification types
for every phone number:
o
Contact ID (ADEMCO),
o
User SMS,
o
Egida-2 SMS,
o
Egida-3 SMS,
o
CSD,
o
CSD (DC-09),
o
GPRS (DC-09)
o
Voice Message,
o
Phone Call.
•
Provides filtering messages to be transmitted based on the programmable notification filter.
•
Polls Orion system devices and transmits messages from these devices:
o
Under an S2000/S2000M control console or Orion Pro Workstation (Slave 1 and Slave 2
modes),
o
Without a control panel (Master mode).
•
Enables remote controlling by received SMS messages:
o
Arming/disarming own alarm loops,
o
Arming/disarming partitions (Slave 1 and Slave 2 modes),
o
Requesting for partition states (Slave 1 and Slave 2 modes),
o
Switching the relay outputs on/off,
o
Changing phone numbers for subscribers,
o
Changing Object Number.
•
Provides light and sound indication of conditions of its own alarm loops, power supplies and
communication channel; this indication can be disabled.
•
Provides sending test messages for link control.
•
Provides automatic (and on-request) checking of the balance on the SIM cards.
•
Provides protection against reading out the configuration.
•
Transmits events about lost/restoring of communication channels with subscribers to the
S2000M control panel and to directions for transmission.
OPERATION MODES
The UO-4S provides operation in the following operation modes:
Standalone
This mode is intended for standalone use of the panel. In this mode the UO-4S does not
communicate data over the RS-485 interface.
•
The UO-4S monitors and transmits only its own states of alarm loops, power conditions, and
communication conditions.
•
Alarm loops are armed and disarmed by means of a credential, an operating alarm loop, or
remotely via GSM channel.