31
Relay Outputs
To program relays it is necessary to select Relay Type, to give Activation Time during which
every relay is activated in accordance with the defined control tactics, and to select the alarm loops
linked with every relay.
The parameter Activation Time for the relay tactics Switch Off upon Arming can be set to a
value which corresponds to a time in the range of 1 to 10 seconds, with one unit of the parameter being
equal to 0.125 s.
•
Activation Time = 0 – The relay will not be activated.
•
Activation Time = 255 – The relay will operate in accordance with the selected tactics until
linked inputs change their state.
The Activation Time parameter is not applicable to a relay if the relay is assigned with one
of such tactics as Lamp, Communication Failure, and Remote Control. Such relay always
operates in accordance with given tactics until the linked inputs change their state.
When the relay control tactics «Switch Off upon Arming» and «Lock Control» are in use
the relay can be linked only with a single alarm loop.
SIM Card Settings
While using SIM cards it is recommended previously to turn their PIN codes off. However, if it
is required to work with cards for which PIN codes are asked then it is necessary to specify these codes
in the relevant fields for the primary and backup SIM cards.
If it is necessary to ask the balance automatically then the balance request codes should
be typed in the relevant fields of SIM1/SIM2 and the relevant period for automatic
checking in days should be selected.
To turn a PIN off in the device settings switch the panel to the programming mode
without presenting the Master Key (power the panel up closing the reader terminals)