10
Slave 1, Slave 2
This mode is in use when the UO-4S operates as part of Orion integrated security system under an
S2000 or S2000M monitoring and control panel.
Transmitting notifications via UO-4S is supported by S2000 panels of versions 1.12+ and all
versions of S2000M panels.
To transmit notifications from an S2000/S2000M panel through the UO-4S, the
S2000/S2000M panel should be programmed with the help of PProg utility – see the
panel’s manual.
The Slave 1 operation mode is to be selected when panels S2000 or S2000M of versions 2.01-
2.03 are in use.
For control panels S2000M of versions 2.05 and higher and Orion Pro software 1.11 SP2 and
higher the operation mode Slave 2 must be selected.
The UO-4S transmits not physical numbers of zones but unique Contact ID numbers of
zones, readers, relays, and state zones of devices which are assigned to these objects in
PProg for S2000
М
control panels of versions 2.04 and higher or added to the UO-4S
configuration on Zones and Partitions tab for control panels of lower versions.
Numbering of Contact ID zones (relays, device states) in the control panel
configuration (in PProg.exe) must be continuous.
When the UO-4S operates in one of the slave modes all the credentials should be
enrolled in the control panel (up to control panel version 3.0.3), otherwise all messages
about arming and disarming are transmitted without a user number.
When the UO-4S operates in the Slave 1 / Slave 2 operation mode:
•
The maximum number of partitions is 99;
•
The maximum number of zones is 128;
•
The maximum number of user credentials is 255.
Master
This mode is intended for transmitting notifications from such Orion devices as S2000-4, S2000-
KDL, Signal-20, Signal-20M, Signal-20P, Signal-10, S2000-ASPT in a system without an
S2000/S2000M control panel or Orion Pro workstation.
When the UO-4S operates in the Master operation mode:
•
The maximum number of partitions is 99;
•
The maximum number of zones is 128;
•
The maximum number of user credentials is 255;
•
There cannot be two or more UO-4S in the Master mode used in the same network. Also no
UO-4S in the Master mode can be used in one network together with a control panel.
•
The XP2 jumper (see Figure 1) must be removed (open) for the Master mode. For all other
modes (Standalone, Slave 1, Slave 2) the jumper must be put on (closed).