15
Table 5 (continued)
Tactics «Alarm Output» **
All the alarm loops are armed
On
Otherwise
Off
Tactics «Switch Off upon Arming»***
A command to arm the alarm loop is given
The relay is turned off for a time
Otherwise
The relay is turned on
Tactics «Remote Control»
An SMS-command to turn the relay on has
been received
The relay is turned on for a given time; if no time is given
then the relay is on steady
An SMS-command to turn the relay off has
been received
The relay is turned off
Tactics «Communication Failure»****
Normal communication with subscribers
Off
Loss of communication at least with one
subscriber
On
*
When the tactics «Lamp» is used with fire and panic alarm loops the relay is turned off when the alarm
loop is OK because fire and panic alarm loops are always armed.
**
Tactics «Alarm Output» doesn’t operate with fire alarm loops, i.e. the relay changes its state neither in
case of a fire nor in case of an open/short circuit failure of the alarm loops.
*** The time for which the relay will be turned off can be set in the limits of 1 to 80 conventional units
provided that one conventional unit of the parameters is equal to 0.125 s. For example, in order to give
time for the relay to be turned off to 5 seconds the value of 40 should be entered (for a fire alarm loop the
relay can be turns off only on being armed by iButton from such state as Disarmed or Fire Alarm
credential to perform power-on reset for the detector).
**** Tactics «Communication Failure» may not work is the subscriber uses Who Called service of similar.
Also the tactics is not operable in case of using SMS-protocols.
For tactics «Switch Off upon Arming» and «Lock Control» the relay can be linked only
with a single alarm loop.
CREDENTIAL PROGRAMMING MODE
The UO-4S can operate partitions by means of credentials. The panel can be programmed for
using credentials by means of UProg or immediately in the mode of programming credentials. To switch
the UO-4S to the credential programming mode, the Master Key should be used.
In the process of programming the Master Key all previously saved credential data are
cleared.
The Master Key is not designed for arming and disarming.
Programming the Master Key:
1.
Disarm all alarm loops assigned with the Intrusion and Entrance types.
2.
Power off the UO-4S.
3.
Use a piece of wire to couple the contacts of the UO-4S reader and keep the contacts coupled.
4.
Power up the UO-4S.
5.
Wait until the panel issues the Master Key Programming signal (two short double beeps and
then one long sound).
6.
Open the contacts of the reader of the UO-4S and then quickly, within no more than 10
seconds briefly touch the UO-4S reader by the iButton. The panel beeper issues a beep. It
means that the Master Key is written to the UO-4S memory.