21
SMS (Egida-2), SMS (Egida-3)
Transmitting SMS to a central monitoring station with Egida rev.02 or Egida rev.03 software
respectively. Notification formats are shown in Appendix C and Appendix D. Receivers can be an
UOP-3 GSM and a GSM modem. Description of SMS for the protocols Egida-2 and Egida-3 is not
available for editing by user.
Voice Messages
All voice messages begin with the phrase “Attention, the message from the object number…”
followed by the code of the object and the text of the message itself. The panel cannot synthesize object
descriptions by voice, so the messages contain only the numbers of partitions, zones, and users
(credentials).
A voice message for a current direction is considered to be delivered if it has been heard in
full including the given number of message repeats. Otherwise the UO-4S will try to
establish communication once more and to transmit the notification so many times as
defined for the voice message notifications.*
* If the Who Called option (or similar) is activated for the subscriber then the number will not be
called repeatedly.
Phone Call
For this notification type the UO-4S dials to the subscriber and hangs up; this type of notification
is used to inform the subscriber that an event has happened without describing the event.
CSD (D
С
-05)/CSD(DC-09)
If this type of notifications is selected then data are transmitted via GSM network over the fax-
data channel in digital form with the rate of 9.6 Kbit/s. A receiver can be UOP3-GSM or GSM modem
for CSD (D
С
09).
Many carriers can transmit and receive data via CSD only after special connecting of this
service.
GPRS (DC09)
Notifications are transmitted using GPRS in the protocol «DC-09» to a specified IP address and
port. Data can be received on a PC immediately (without panels) provided that Egida-3 Central
Monitoring Station software or other software supporting this protocol is installed on the PC.
If the transmission over GPRS is enabled it is of the highest priority in its group. While operating
via GPRS, by default data are encrypted using the default key (encryption keys are adjusted in
UProg.exe and Egida-3) provided that encryption can be disabled when necessary.
Filtering
To minimize data to be transmitted and to provide receiving only the required information, an
event filter can be adjusted for every subscriber number. The filter criteria are alarm loop numbers (for
the standalone mode) and types of event.
Grouping
To provide redundancy, phone numbers can be combined into groups. If a group number is the
same for all phone numbers then the panel will transmit notifications only to one number from the
group, namely the first number which the panel has reached. If group numbers are different then the
UO-4S will consistently transmit notifications for all phone numbers assigned with different group
numbers.