12
Table 2. Internal Beeper
Event (Condition)
Beeper Performance
Norm
Off
Alarm, Fire
Interrupted sound (Can be enabled / disabled via UProg)
Short/Open Circuit Failure
Beeps once per second
Arming
Two beeps upon arming
(Can be enabled/disabled by means of UProg)
Disarming
Turns off (if it was on) and then beeps once
(Can be enabled/disabled by means of UProg)
Arming Delay
Beeps once per two seconds
Within 15 seconds before the end of the delay the beeper
starts beeping twice per second
Arming Failed
A beep
An unknown credential is presented
A long sound
Saving configuration to the device by means of
UProg
A beep
Entering the mode of programming credentials
Three pairs of beeps
Communication Fault
*
Beeps once per two seconds
Test is run remotely from the S2000M panel
A long sound
*
- The internal sounder can be disabled for communication line faults in UProg.
Table 3. Indicators of Reader and Patrol Check Circuit
Event (Conditions)
Indicator Performance
Disarmed
(All intrusion alarm loops are disarmed)
Off
Armed
(One or more intrusion alarm loops are
armed)
Illuminates when power is in norm, otherwise flashes once
per two seconds)
Alarm
(One or more alarm loops are in Intrusion
Alarm, Fire Alarm, Entrance Alarm)
Flashes four times per second
Arming Failed
(One or more alarm loops are in the Arming
Failed status)
Arming Delay
(One of the alarm loops of the Entrance type
is in the Arming Delay status)
Flashes ones per two seconds
Fault
(One or more alarm loops are in the
Short/Open Circuit Failure status)
Flashes twice per second
12 V Power Failure
Flashes ones per two seconds
First touch by the credential in the quiescent
mode (see Note below)
Switches on for a short time three times and then indicates
the current state of the alarm loops associated with the
current credential (only for reader LED)
Disarming is performed after the second
touch by the credential
The indicator is switched off
Arming is performed after the second touch
by the credential
The indicator is switched on
Patrol Check
Patrol Check Circuit indicator flashes twice with three
flashes
Unknown credential is presented
Indicator of the reader flips its state for 1 s
Programming mode
The indicator is switched off
Master Key Programming mode
The reader indicator is on
Note:
After a single touch by the credential the indicator of the reader within 30 seconds indicates the status of a
group of alarm loops associated with this credential. Arming and disarming is performed after a second touch of the
reader by the same credential within 30 seconds.