6.4. Troubleshooting
6.4.1. No network connection
Check the cabling / switch.
Check whether an IP address has been duplicated.
Check the network settings on the PC: The subnet and the subnet mask settings must be the
same as those for the controller.
Check the firewall / anti-virus programs on the PC.
Check the Lifeguard settings.
6.4.2. In error stop mode DC2115WUX CM / DC2110W X CM
1st
Log in to the device via a web browser.
2nd
Determine the cause of the fault (Diagnostics > PLC Log/System Log).
3rd
Correct the fault.
4th
Restart the device (press “Reset” on the device).
The device is now ready for use.