USER HANDBOOK 1.2
B-PRIMIS DC/ET PRIME 2110W X C,
2115WUX C
Page 1: ...USER HANDBOOK 1 2 B PRIMIS DC ET PRIME 2110W X C 2115WUX C ...
Page 2: ...her countries EtherCAT is a registered trademark and patented technology licensed from Beckhoff Automa tion GmbH Germany CiA and CANopen are registered trademarks belonging to CAN in Automation e V ARM and Cortex are registered trademarks belonging to ARM Limited PROFINET is a registered trademark belonging to PROFIBUS Nutzerorganisation e V Modbus is a registered trademark belonging to the Modbus...
Page 3: ..._EN docx 3 Change log Version Date Description 0 2 10 04 2018 HB first draft 0 8 12 06 2018 Addition of graphics Corrections change to new layout 0 9 18 06 2018 Corrections chapter added Counter and web interface 1 0 26 06 2018 First version 1 1 05 12 2018 Modification to the mechanism new group names 1 2 14 12 2018 Corrections after review 1 3 21 12 2018 Corrections IP protection ...
Page 4: ...2 1 Safety instructions 12 Working on the device 12 3 PRODUCT DESCRIPTION 13 3 1 Overview 14 3 1 1 Overview DC2115WUX CM 14 3 1 2 Overview DC2110W X CM 15 3 1 3 Overview ET2115WUX CS 16 3 1 4 Overview ET2110W X CS 17 3 2 Scope of delivery and accessories 18 Scope of delivery 18 Accessories 18 3 3 Product features 18 4 INSTALLATION 20 4 1 Preparation for installation Front installation DC ET2115WUX...
Page 5: ...S Configuration 54 6 2 4 ET2115WUX CS ET2110W X CS web terminal configuration 56 6 3 Operation 58 6 3 1 Status displays only DC PRIME 58 6 3 2 Function key S1 only DC PRIME 59 6 3 3 Real time clock with buffer battery DC2115WUX CM DC2110W X CM 59 6 3 4 microSD card 60 6 4 Troubleshooting 61 6 4 1 No network connection 61 6 4 2 In error stop mode DC2115WUX CM DC2110W X CM 61 7 MAINTENANCE UPKEEP 62...
Page 6: ...RIME 2110W X C 2115WUX C Berghof Automation GmbH Harretstraße 1 72800 Eningen www berghof automation com 270011X00_B PRIMIS_ET DC PRIME 2110W 2115W_EN docx 6 13 1 Information on copyright and software licence 76 13 2 List of figures 76 ...
Page 7: ...s B PRIMIS DC PRIME DC2110W Dialog Controller X CM and DC2115WUX CM B PRIMIS ET PRIME Ethernet Terminal ET2110W X CS and ET2115WUX CS It contains information on the following topics Applications Safety Mechanical design Electrical design Connections Start up Upkeep and maintenance Decommissioning Disposal Always keep this user handbook available alongside the product 1 2 Symbols and visual depicti...
Page 8: ...sure your personal safety and avoid any damage to property The indications have the following meanings DANGER Serious injury or death Non compliance with the safety features will result in death or serious injury Take preventive measures WARNING Possible serious injury or death Non compliance with the safety features may result in death or serious injury Take preventive measures CAUTION Possible m...
Page 9: ...ing order The user handbook must always be kept legible and fully available Only sufficiently qualified and authorised personnel may carry out the assembly installation start up and maintenance of the device These authorised personnel must receive regular training on all relevant occupational health and safety and environmental protection issues and must be fully familiar with the contents of this...
Page 10: ... exposed to direct UV radiation Max ambient temperature inside and outside the control cabinet in accordance with the technical data see Technical data Qualified project planning and design proper transport storage installation use and careful mainte nance are essential to the flawless and safe operation of the automation system The automation system may only be used within the scope of the data a...
Page 11: ...e has been stored or transported in cold weather or under conditions or large fluctua tions in temperature do not start to operate it until it has acclimatised to room temperature for the place it is used If condensation is present wait at least 12 hours before starting to operate the device 1 8 Unpacking Or receipt of the device a check must be made that it is complete and undamaged Check the pac...
Page 12: ...nal behaviour All types of failure must be considered at the system level and the associated preventative measures identified If necessary request information from your automation system provider 2 1 Safety instructions The device may be operated only when it is in good working order Exposed sharp edges pose an inju ry risk If you discover damage to the front glass of the device do not continue to...
Page 13: ... the B PRIMIS ET PRIME product group ET2110W X CS and ET2115WUX CS are input devices with a display for connection to a control system for machines or systems The terminal shows the CODESYS Web visualisation or CODESYS Target visualisation irrespective of whether the visualisation originates from a Berghof PLC control unit or some other CODESYS control unit ET211x Ethernet Terminals can be connect...
Page 14: ...Designation Item Designation 1 Display 15 6 inch X6 EtherCAT ETH1 2 LEDs PWR Run Stop Error X8 CAN bus 3 LEDs Power digital I O X9 RS 232 RS 485 4 Earth connection X11 Debug interface do not use this it is for use only by Berghof Service Engineers X1 Power supply digital inputs outputs S1 Function key X2 Analogue inputs S2 Terminating resistor CAN 120 Ohm X3 USB 2 0 S3 Terminating resistor RS 485 ...
Page 15: ...ation Item Designation 1 Display 10 1 inch X6 EtherCAT ETH1 2 LEDs PWR Run Stop Error X8 CAN bus 3 LEDs Power digital I O X9 RS 232 RS 485 4 Earth connection X11 Debug interface do not use this it is for use only by Berghof Service Engineers X1 Power supply digital inputs outputs S1 Function key X2 Analogue inputs S2 Terminating resistor CAN 120 Ohm X3 USB 2 0 S3 Terminating resistor RS 485 120 Oh...
Page 16: ...docx 16 3 1 3 Overview ET2115WUX CS Fig 3 Overview ET2115WUX CS rear view Item Designation Item Designation 1 Display 15 6 inch X8 Debug interface do not use this it is for use only by Berghof Service Engineers 2 Earth connection X100 Power supply X3 USB 2 0 S1 Function button do not use this it is for use only by Berghof Service Engineers X4 Ethernet ETH0 LED LEDs PWR Run Stop Error ...
Page 17: ...docx 17 3 1 4 Overview ET2110W X CS Fig 4 Overview ET2110W X CS rear view Item Designation Item Designation 1 Display 10 1 inch X8 Debug interface do not use this it is for use only by Berghof Service Engineers 2 Earth connection X100 Power supply X3 USB 2 0 S1 Function button do not use this it is for use only by Berghof Service Engineers X4 Ethernet ETH0 LED LEDs PWR Run Stop Error ...
Page 18: ...g clip SMALL 8 14 ET2110W X CS ET2115WUX CS E I O plug 2 pin black order no 204801800 Securing clip SMALL 8 14 3 3 Product features Installation The device is designed for installation in a front panel or in a control panel in a rough industrial envi ronment Processor In its the basic configuration the device is equipped with an 800 MHz ARM CPU with a Cortex A9 core Ethernet 1 Ethernet interface w...
Page 19: ...X CM The device incorporates digital inputs outputs and analogue inputs Real time clock DC2110W X CM DC2115WUX CM A software interface permits the current time and date to be set and read on a real time clock with bat tery back up microSD card DC2110W X CM DC2115WUX CM The standard commercial microSD card interface SDHC up to max 32 GB allows data to be written to memory cards or read from memory ...
Page 20: ...llation from the front into a rectangular cut out on a panel The support material must be rigid and be from 1 to 3 mm thick Fig 5 Dimensions DC2115WUX CM ET2115WUX CS Requirements To allow sufficient air circulation it must be ensured that the device has a clear space of at least 20 mm all round at the rear The max ambient temperature inside the control cabinet must not exceed 55 C in operation Th...
Page 21: ... material can lead to mechanical stresses and cracks in the front face or malfunctioning of the touch screen Make sure that the mounting points of the device are all in a common plane with no more than max imum 0 5 mm variation Fig 6 Installation cut out DC2115WUX CM ET2115WUX CS Cut a rectangular installation cut out in the support material Height 231 mm Width 381 mm Max corner radius 1 5 mm Opti...
Page 22: ...CM ET2110W X CS Requirements To allow sufficient air circulation it must be ensured that the device has a clear space of at least 20 mm all round at the rear The max ambient temperature inside the control cabinet must not exceed 55 C in operation The support material for the installation cut out must be flat sufficiently stable and be from 1 to 3 mm thick NOTE Damage to the device Installation on ...
Page 23: ...ngen www berghof automation com 270011X00_B PRIMIS_ET DC PRIME 2110W 2115W_EN docx 23 Fig 8 Installation cut out DC2110W X CM ET2110W X CS Cut a rectangular installation cut out in the support material Height 163 mm Width 242 mm Max corner radius 1 5 mm Optimum thickness of the support material 1 0 to 3 0 mm ...
Page 24: ...cut out Requirements The securing clips must not be attached to the device 1st Making sure the alignment is correct push the device evenly into the installation cut out NOTE Damage to the device If installation is performed carelessly the device can fall out of the installation cut out or be damaged Do not tilt the device Restrain the device against falling until the securing clips have been tight...
Page 25: ...cx 25 Fig 10 Mounting the securing clips 3rd Secure the device with 2 securing clips Insert the securing clips into the cover at diagonally op posite points and tighten the screws finger tight Fig 11 Fully tightening the securing clips 4th Insert the other securing clips and tighten the screws in all the securing clips equally DC ET2115WUX 14 securing clips DC ET2110W X 8 securing clips ...
Page 26: ...xternal power supply meets the required specifi cations type K to 61131 2 External power supply 24 V DC Supply voltage 24 V DC SELV 15 20 Ripple current propor tion Max 5 The direct voltage level must not fall below 20 4 V Power consumption ET2110W X CS Total max 0 6 A at 24 V DC peak current 1 2 A ET2115WUX CS Total max 0 7 A at 24 V DC peak current 1 2 A DC2110W X CM Total max 0 8 A at 24 V DC p...
Page 27: ...wer feeds including peripherals ET2110W X CM ET2115WUX CM Connect the power supply to plug X100 according to the following table Fig 12 Power supply plug X100 Power supply plug X100 Pin Designa tion Assignment 9 L0 24 V Power supply 24 V DC 15 20 ET2110W X CS max 0 6 A peak current 1 2 A ET2115WUX CS max 0 7 A peak current 1 2 A 11 GND M0 GND The following counterparts have been tested for the SC ...
Page 28: ...t 1 8 I O digital inputs and outputs see Digital inputs and outputs DC2115 9 L0 24 V Power supply 24 V DC 15 20 internal PLC DC2110W X CM max 0 8 A peak current 1 2 A DC2115WUX CM max 0 9 A peak current 1 2 A 10 L1 24 V I O Feed to digital output max 2 A for 0 5 A per output for I O 11 M0 GND 12 L0 24 V Power supply 24 V DC 15 20 PLC internal processing max 1 2A DC2110W X CM max 0 8 A peak current...
Page 29: ...erghof Automation GmbH Harretstraße 1 72800 Eningen www berghof automation com 270011X00_B PRIMIS_ET DC PRIME 2110W 2115W_EN docx 29 5 2 Data connections 5 2 1 Block circuit diagram DC2115WUX CM DC2110W X CM Fig 14 Block circuit diagram DC2115WUX CM DC2110W X CM ...
Page 30: ...115WUX C Berghof Automation GmbH Harretstraße 1 72800 Eningen www berghof automation com 270011X00_B PRIMIS_ET DC PRIME 2110W 2115W_EN docx 30 5 2 2 Block circuit diagram ET2115WUX CS ET2110W X CS Fig 15 Block circuit diagram ET2115WUX CS ET2110W X CS ...
Page 31: ... 1 or 3 IEC 61131 2 They are designed for nominal input voltages of 24 V The input signals are transmitted internally on a cyclical basis for process data processing An open input is interpreted as static 0 The inputs also have a common reference potential GND The following counterparts have been tested with the S2C SMT 3 5 Weidmüller connector and are approved for use with the device B2CF 3 50 12...
Page 32: ...on response threshold yes electronic voltage limitation typ 7 A The current is limited electronically Activation of short circuit protection results in thermal overload and tripping of thermal overload protection Permissible limits based on cold state max 10 000 short circuits overall duration max 500 hours Status under unclear operating conditions Logical 0 If the supply voltage is insufficient a...
Page 33: ...ded connection cables Cables over 30 m in length must be shielded Cable cross section within the control cabi net 0 14 1 5 mm 26 16 AWG Aim for plug connector limits to UL specifications Field wiring according to regulations and standards Comply with all local regulations and the stipula tions of DIN EN 61131 2 Rated load voltage 24 V DC SELV Delay time 1 ms Applies for transitions from 0 to 1 and...
Page 34: ...erghof automation com 270011X00_B PRIMIS_ET DC PRIME 2110W 2115W_EN docx 34 Fig 18 Circuit diagram of the principles of positive switching input Fig 19 Operating ranges of the digital inputs type 1 3 negative switching Item Designation Item Designation 1 ON range 3 Transition range 2 Signal noise ratio 1 V 4 OFF range ...
Page 35: ...ng inputs are linked to the signals of the other unipolar inputs There is no changeover Available configurations of the counting inputs Up Down counter Pulse Direction counter Quadrature decoder One of the counting inputs can also be used as a capture input This configuration requires 3 of the in puts partially as a CNT input or CAPT input The flanks for Up Down or Pulse can be defined as ris ing ...
Page 36: ... Function Value Description Number of counters 2 Signal voltage 1 DC 15 28 V 0 DC 3 3 V Pulse width within the valid level for at least 1 µs Max frequency Signal Counter 500 kHz 1 counts s Special installation instructions are applicable to 100 kHz At the maximum counting frequency the signal generator must ensure a flank steepness of at least 20 V µs Min Pulse width 1 µs Per level counter resolut...
Page 37: ...o the general GND of the control panel or to the M on the con trol unit GND and AGND are already connected within the control unit via a special filter AGNDs may not be connected directly to the equipotential bonding conductor PE of the ma chine or system Long cables and wires with a small cross section lead to voltage drops and deviations in PT100 0 measurements due to resistance of the lead Thes...
Page 38: ...ng rate Operating mode AI PT 250 ms In operating mode AI PT calculations are carried out after the millisecond sampling rate A new val ue is available in the user program every 250 ms Digital filtering Available filter settings Time range for averaging Time range for averaging Operating mode AI PT 0 1 ms 0 25 s 10 10 ms 2 5 s 100 100 ms 25 s 1000 1 000 ms 1 s 250 s If filtering is active an averag...
Page 39: ... channel is switched on or off Max error at 25 C 0 8 2 C Temperature coeffi cient 40 ppm K 0 4 mV K Digital resolution 24 bit Data format in user program 32 bit real floating point number in millivolts mV Maximum permissible permanent overload Max 30 V compared to AGND 30 V max voltage at AI channel Value of least signifi cant bit 1 2 µV Output of digital value in case of overload If a voltage of ...
Page 40: ...sensors PT100 and PT1000 acc to EN 60751 Platinum sensors of accuracy classes AA A B and C may be used Measuring range 40 to 200 C Measuring current RMS 0 3 mA Conversion time 250 ms Max error at 25 C 2100 ppm 0 5 C Temperature coeffi cient 50 ppm K 0 012 C K Digital resolution 24 bit Data format in user program 2 32 bit real floating point number in Ohms Ω and degrees Celsius C Linearisation The ...
Page 41: ...ection voltage input Only use the corresponding AGND for each voltage input Do not connect AGNDs from different channels AGNDs from different channels must always be connected separately to the plug X1 Do not connect to the common GND The required connections can already be found on the cir cuit board Cables to the analogue sensors encoders should be connected as directly as possible avoid the use...
Page 42: ... cuit board Cables to the PT100 0 sensors should be connected as directly as possible avoid the use of terminals and terminal blocks Only connect PT100 0 sensors to AI U T channels 2 wire measurement Resistance can result in a measurement error which in the case of long cables with a small cross section can be up to 10 If the temperature of the sensor is known this deviation can be subtracted by t...
Page 43: ...thernet adapter has one 10 100 Base T RJ 45 port for connection to the network Fig 25 Ethernet interface X4 Assignment of Ethernet interface plug X4 Pin Assignment Pin Assignment 1 TX 5 NC 2 TX 6 RX 3 RX 7 NC 4 NC 8 NC LEDs LED Colour Meaning to IEEE 802 3 clause 25 LNK RCV green Link Data Receive Flashing connection active data transfer in pro gress Off no connection established SPEED yellow On 1...
Page 44: ...has two RJ 45 10 100 Base T interfaces for networking The Ethernet interface X6 can be used as the EtherCAT master Fig 26 EtherCAT interface X6 Assignment of EtherCAT interface connector X6 Pin Assignment Pin Assignment 1 TX 5 NC 2 TX 6 RX 3 RX 7 NC 4 NC 8 NC LEDs LED Colour Meaning to IEEE 802 3 clause 25 LNK RCV green Link Data Receive Flashing connection active data transfer in pro gress Off no...
Page 45: ... are being transferred can render the USB stick un usable Open files which can no longer be accessed because the USB stick has been removed can block the device Therefore ensure that all operations are complete before removing the USB stick NOTE Damage to property and malfunctions due to data loss The USB interface is protected against overloading 0 5 A In the event of a short circuit during opera...
Page 46: ...ace Standard ISO 11898 Maximum Baud rate 1 MBit s Lowest adjustable Baud rate 50 kBit s Contacts Electrically isolated Assignment to CiA303 Fig 28 CAN interface X8 Assignment of CAN interface connector X8 Pin Assignment Pin Assignment 1 CAN_H 5 NC 2 CAN_L 6 NC 3 ISO GND 7 ISO GND 4 NC 8 NC If the CAN interface is located at the start or end of the CAN bus topology set switch S2 to ON in order to s...
Page 47: ...mum baud rate for both interfaces 115 kBd Fig 29 RS 232 RS 485 interface X9 Pin assignment for RS 232 RS 485 interface connector X9 Pin Assignment software inter face Pin Assignment software inter face 1 RS 232 RX COM 1 5 RS 485 Tx Rx COM 2 2 RS 232 TX COM 1 6 NC 3 NC 7 reserved 4 RS 485 Tx Rx COM 2 8 ISO GND The RS 485 interface is soft terminated in the dialogue controller with 560 Ω If the inte...
Page 48: ...ned statuses for logical 1 A B 0 2 V and logical 0 A B 0 2 V Undriven bus The bus termination must be as asymmetric as possible to ensure the greatest possible signal noise ratio to reduce the symmetrical signal noise ratio In order to achieve the necessary voltage difference between the signals a suitable resistor net work must be used as the line termination The necessary size of the resistors i...
Page 49: ...ting any work on the device switch off all power feeds including those to any connected peripherals sensors and programmable devices etc with independent power supplies NOTE Damage to property Before connecting the power supply ensure that all cabling and the polarity of all the connections are correct Switching on The device does not have an on off switch The device starts automatically when the ...
Page 50: ...sure that all cabling and the polarity of all the connections are correct 1st Supply the device with power 24 V After the start the current IP address and network mask of the device are shown at the top right of the display 2nd Connect the device to a programming computer using a network cable X4 and network switch 3rd Open a web browser on the programming computer 4th Enter the IP address of the ...
Page 51: ...ttings 8th Click on the Network link The Network Configuration page is displayed Fig 33 Network Configuration page 9th Check the network settings and if desired make changes in the respective text boxes Configuration DC211x ETH0 X4 ETH1 X5 10th Save the settings by clicking on Save 11th Additional settings can also be viewed and or modified on the web configuration page for example system time dis...
Page 52: ...by clicking on Re boot Module The device is now configured and ready for use 6 2 2 DC2115WUX CM DC2110W X CM on screen config NOTE Damage to property Before connecting the power supply ensure that all cabling and the polarity of all the connections are correct 1st Supply the device with power 24 V After the start the current IP address and network mask of the device are shown at the top right of t...
Page 53: ...ed IP address network mask gateway 4th Press the Next button The page with the summary of the network settings appears Fig 36 Summary of the network settings 5th To change other settings or to correct the changes press the Back button 6th If no settings were changed press the OK button The main screen of the device will be displayed or Press the Save button The settings will be saved and the devic...
Page 54: ... with the correct settings before it can be used NOTE Damage to property Before connecting the power supply ensure that all cabling and the polarity of all the connections are correct 1st Supply the device with power 24 V After the start the current network settings are displayed server IP IP address and network mask Fig 37 Start page with network settings 2nd Press the Configuration button A page...
Page 55: ...ssary press the Edit button and change the network settings as required IP address network mask gateway 5th Press the Next button The page with the settings for the server IP and Lifeguard appears Fig 40 Setting the server IP 6th If necessary press the Edit button and change the server IP as required 7th Press the Expert button to change the Lifeguard setting The page with the Expert settings will...
Page 56: ...ngs will be saved and the device will restart automatically 11th Connect the device to the controller using the network cable The device is now configured and ready for use 6 2 4 ET2115WUX CS ET2110W X CS web terminal configuration Before the device can be used in web terminal mode it must be connected to the network with the cor rect settings before it can be used Please read ET2115W X CS ET2110W...
Page 57: ...e device starts its integral browser and blocks the Configuration button Once this has happened the only way to access the Configuration button is to restart the device again 6th Directly after the start up press the Configuration button 7th Press the Next button to skip the IP settings until the page with the Visu URL appears 8th Press the Edit button 9th Input the desired URL and confirm by pres...
Page 58: ...module mode and any er ror messages Location of the operating status LEDs The Run Stop and Error LEDs display the system status Fig 43 Location of the operating status LEDs LED Meaning 1 PWR green shows that the power supply to the electronics is correct 2 Run Stop yel low green red shows the system statuses 3 Error red shows the device has been stopped due to an error Meaning of the LED displays ...
Page 59: ...y Toggle between PLC run and stop mode Press and hold Stop the PLC with resetting of variables cold re set 6 3 3 Real time clock with buffer battery DC2115WUX CM DC2110W X CM Setting the date and time The time can be set via the web configuration page or via the CODESYS V3 library Changing the battery The battery is not designed to be changed by the user the manufacturer should be contacted in ord...
Page 60: ...rt or remove a microSD card only when the device is switched off NOTE Loss of data microSD cards do not have their own write protection system Ensure that no data is deleted or overwritten by accident Inserting a microSD card 1st Switch the device off 2nd Insert the microSD card into the microSD card slot 3rd Switch the device on again The microSD card is now ready for data transfer read write and...
Page 61: ...dress has been duplicated Check the network settings on the PC The subnet and the subnet mask settings must be the same as those for the controller Check the firewall anti virus programs on the PC Check the Lifeguard settings 6 4 2 In error stop mode DC2115WUX CM DC2110W X CM 1st Log in to the device via a web browser 2nd Determine the cause of the fault Diagnostics PLC Log System Log 3rd Correct ...
Page 62: ... etc with independent power supplies If the device is used correctly it should not require maintenance Make sure all the ventilation holes are kept free of obstructions Do not open the device If work is required on the device necessary contact customer service 7 2 Cleaning NOTE Damage to the front panel The front panel is of glass and must not be exposed to any mechanical or chemical stress Do not...
Page 63: ...s from the power supply 2nd Unplug all plug connectors and cables NOTE Damage to the device If uninstallation is performed carelessly the device can fall out of the installation cut out or be damaged Do not tilt the device Secure the device against falling especially when taking it out of the installation cut out Fig 45 Undoing the screws 3rd Undo the screws on all the securing clips equally DC ET...
Page 64: ...aße 1 72800 Eningen www berghof automation com 270011X00_B PRIMIS_ET DC PRIME 2110W 2115W_EN docx 64 Fig 46 Removing the securing clips 4th Removing the securing clips Fig 47 Pushing the device out of the installation cut out 5th Push the device evenly forwards out of the installation cut out ...
Page 65: ...licable The following options are available for disposal of the device Disposal by the manufacturer Unless agreed otherwise devices can be sent back for disposal Disposal in accordance with regional regulations Dismantle the device and disassemble it completely into its component parts Send the metal parts for metal recycling Sort the electronic parts circuit boards drives etc Dispose of the elect...
Page 66: ...olatile memory FRAM 100 kB Dimensions and weight Dimensions WxHxD 392 x 242 x 55 mm 259 x 177 x 55 mm Weight approx 3 kg approx 2 5 kg Operating conditions Operating temperature 0 C to 55 C front and rear of the device in compliance with installa tion requirements Relative humidity max 85 non condensing Transport and storage Operating temperature 20 C to 70 C Relative humidity max 85 non condensin...
Page 67: ...age Protection rating IP20 front IP44 Power supply 24 V power Supply voltage 24 V DC 15 20 SELV max ripple component 5 Power consumption Max 0 8 A peak current 1 2 A at 24 V DC fused Power consumption dig Out puts Depending on the output load max 2 A continuous rating Protection against reverse po larity yes Ethernet interfaces No type of interface 1x 10 100 Base T Connection system RJ45 EtherCAT ...
Page 68: ...e clock yes with battery back up microSD card slot 1x microSD card optional I O Digital IN 4x Digital OUT 4x 0 5 A Analogue IN 4 x universal analogue inputs 10 V 10 V 2 x PT100 PT1000 Resolution 24 bit 2x 10 10 V PT100 PT1000 with 2 wire 2x 10 10 V or return conductor for 3 wire Battery Type Panasonic VL2020 or similar Lifespan 10 years depends on operating temperature Storage 1 year without volta...
Page 69: ...ht approx 3 kg approx 2 5 kg Operating conditions Operating temperature 0 C to 55 C front and rear of the device in compliance with installa tion requirements Relative humidity max 85 non condensing Transport and storage Operating temperature 20 C to 70 C Relative humidity max 85 non condensing Operation Installation Removable securing clips Certification to product standards EN 61010 2 201 EN 611...
Page 70: ...e EN 61131 2 500 V DC test voltage Protection rating IP20 front IP55 Power supply 24 V power Supply voltage 24 V DC 15 20 SELV max ripple component 5 Power consumption Max 0 8 A peak current 1 2 A at 24 V DC fused Protection against reverse po larity yes Ethernet interface No type of interface 1x 10 100 Base T Connection system RJ45 Protocols TCP IP USB interface No type of interface 1x host USB 2...
Page 71: ...fication plate Item Designation Item Designation 1 Device type description 6 Customer no 2 Identification no Article no serial no and version as delivered condition 7 Supply voltage und maximum current consumption 3 Date of manufacture year week 8 QR code Identification no 4 Manufacturer s address 9 CE mark 5 Mac addresses 10 Manufacturer s mark trademark The Version field delivered version specif...
Page 72: ...1X00_B PRIMIS_ET DC PRIME 2110W 2115W_EN docx 72 10 4 Identification The characteristics of the device can be decoded from the identification key ET2110W X CM and ET2115 WUX CM are members of the B PRIMIS ET PRIME device series DC2110W X CM and DC2115 WUX CM are members of the B PRIMIS DC PRIME device series Fig 49 Identification key DC ET21xx ...
Page 73: ...Standards Applicable directives EMC directive 2014 30 EU RoHS directive 2011 65 EU Applicable standards Programmable Logic Controllers part 1 General information EN 61131 1 Programmable Logic Controllers part 2 Equipment requirements and tests EN 61131 2 Safety provisions DIN EN 61010 2 201 Technical documentation for assessing electrical and electronic equipment in respect of re striction of haza...
Page 74: ...0W 2115W_EN docx 74 11 2 Declaration of conformity The declarations of conformity can be found on our website www berghof automation com and are available for downloading in respect of each product Example of a path Products Controllers PLC Display PLC Capacitive Product On each product page there is a link for downloading the declaration of conformity Fig 50 Download menu ...
Page 75: ...n GmbH Harretstr 1 72800 Eningen Germany T 49 7121 894 183 F 49 7121 894 100 e mail support controls berghof com www berghof automation com 12 2 Addresses CAN in Automation international manufacturer and user organisation for CAN users in automation CAN in Automation e V CiA Am Weichselgarten 26 91058 Erlangen headquarters can cia de www can cia de EtherCAT Technology Group ETG Headquarters Ostend...
Page 76: ... 8 Installation cut out DC2110W X CM ET2110W X CS 23 Fig 9 Insertion into the installation cut out 24 Fig 10 Mounting the securing clips 25 Fig 11 Fully tightening the securing clips 25 Fig 12 Power supply plug X100 27 Fig 13 Power supply DC2115 connector X1 with power LED 28 Fig 14 Block circuit diagram DC2115WUX CM DC2110W X CM 29 Fig 15 Block circuit diagram ET2115WUX CS ET2110W X CS 30 Fig 16 ...
Page 77: ...ttings 54 Fig 38 Information page 54 Fig 39 Network settings of the device 55 Fig 40 Setting the server IP 55 Fig 41 Changing the Lifeguard setting 55 Fig 42 Summary of the network settings 56 Fig 41 Switching into web terminal mode 56 Fig 42 Setting the Visu URL 57 Fig 43 Location of the operating status LEDs 58 Fig 44 Function key S1 59 Fig 45 Undoing the screws 63 Fig 46 Removing the securing c...