Learning Advanced Features
83
Group
Code
Name
LCD Display Parameter Setting
Setting
Range
Unit
restart
Number
10
Auto restart
delay time
Retry Delay
1.0
0–60
sec
* Displayed under DRV-06 in an LCD keypad.
Note
•
To prevent a repeat fault from occurring, set Cn.71 (speed search options) bit 2 equal to 1. The
inverter will perform a speed search at the beginning of the operation.
•
If the speed search is not enabled, the inverter will start its operation in a normal V/F pattern and
accelerate the motor.
•
With parameter Pr.08 set to 0 (No), when the inverter is powered up with the run command made,
the inverter will not start. The run command (digital input) must be first turned off, and then
turned on again to begin the inverter’s operation.
Use caution when operating the inverter with Power-on Run enabled as the motor will begin rotating
when the inverter starts up.