335
Troubleshooting
Keypad Display LCD Display
Type
Description
keypad or memory (EEPRom) fault.
ADC Off Set: An error in the current sensing circuit (U/V/W
terminal, current sensor, etc.).
NTC Open
Latch
Displayed when an error is detected in the temperature
sensor of the Insulated Gate Bipolar Transistor (IGBT).
Fan Trip
Latch
Displayed when an error is detected in the cooling fan. Set
Pr.79 to 0 to activate fan trip (for models below 22kW
capacity).
Pre-PID Fail
Latch
Displayed when pre-PID is operating with functions set at
AP.34–AP.36. A fault occurs when a controlled variable
(PID feedback) is measured below the set value and the
low feedback continues, as it is treated as a load fault.
Ext-Brake
Latch
Operates when the external brake signal is provided by
the multi-function terminal. Occurs when the inverter
output starting current remains below the set value at
Ad.41. Set either OU.31 or OU.32 to 35 (BR Control).
Safety A(B)
Err
Latch
Displayed when at least one of the two safety input
signals is off.
Protection Functions for Communication Options
Keypad Display LCD Display
Type
Description
Lost
Command
Level
Displayed when a frequency or operation command
error is detected during inverter operation by controllers
other than the keypad (e.g., using a terminal block and a
communication mode). Activate by setting Pr.12 to any
value other than 0.
IO Board Trip
Latch
Displayed when the I/O board or external
communication card is not connected to the inverter or
there is a bad connection.
Displayed when the
error code continues for
more than 5 sec.
(‘Errc’ -> ’-rrc’ -> E-rc’ -> ’Er-c’ -> ‘Err-‘ -> ’- -rc’ -> ‘Er- -‘ -> ’
- - - -‘ -> ’Errc’ -> …)
ParaWrite Trip Latch
Displayed when communication fails during parameter
writing. Occurs when using an LCD keypad due to a
control cable fault or a bad connection.
Option Trip-1
Latch
Displayed when a communication error is detected
between the inverter and the communication board.
Occurs when the communication option card is installed.
NTC
FAN
PID
XBR
SFB
SFA
LCR
HOLD
IOT
ERRC
S100
PAR
OPT
Summary of Contents for Rsi S Series
Page 2: ......
Page 6: ......
Page 12: ...Preparing the Installation 0...
Page 22: ...Preparing the Installation 10...
Page 70: ...LearningAdvanced Features 58...
Page 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Page 224: ...LearningAdvanced Features 212...
Page 356: ...344...
Page 362: ...Maintenance 350...
Page 381: ...369 TechnicalSpecification...
Page 397: ......