Learning Advanced Features
210
Code
Description
Scale) to "X 0.1" to display the value to the first decimal point. And set
ADV63 (Load Spd Unit) to mpm. Now, the monitoring item 24 Load Speed
is displayed on the keypad display as 300.0 mpm instead of 800 rpm.
Note
Inverter power consumption
Values are calculated using voltage and current. Electric power is calculated every second and the
results are accumulated. Setting CNF-62 (WH Count Reset) value to 1(Yes) will reset cumulated
electric energy consumption. Power consumption is displayed as shown below:
•
Less than 1,000 kW: Units are in kW, displayed in 999.9 kW format.
•
1–99 MW: Units are in MW, displayed in 99.99 MWh format.
•
100–999 MW: Units are in MW, displayed in 999.9 MWh format.
•
More than 1,000 MW: Units are in MW, displayed in 9,999 MWh format and can be displayed up
to 65,535 MW. (Values exceeding 65,535MW will reset the value to 0, and units will return to kW.
It will be displayed in 999.9 kW format).
Operation Time Monitor
Monitor inverter and fan operation time.
Group
Code
Name
LCD Display Parameter Setting Setting Range Unit
CNF*
70
Inverter operation
accumulated time
On-time
0/00/00 00:00
-
min
71
Inverter operation
accumulated time
Run-time
0/00/00 00:00
-
min
72
Inverter operation
accumulated time
initialization
Time Reset 0
No
0–1
-
74
Cooling fan
operation
accumulated time
Fan time
0/00/00 00:00
-
min
75
Cooling fan
operation
accumulated time
initialization
Fan Time
Reset
0
No
0–1
-
*Available on LCD keypad only.
Operation Time Monitor Setting Details
Code
Description
CNF-70 On-
time
Displays accumulated power supply time. Information is displayed in [YY/MM/DD Hr:
Min (0/00/00 00: 00)] format.
CNF-71
Displays accumulated time of voltage output by operation command input.
Summary of Contents for Rsi S Series
Page 2: ......
Page 6: ......
Page 12: ...Preparing the Installation 0...
Page 22: ...Preparing the Installation 10...
Page 70: ...LearningAdvanced Features 58...
Page 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Page 224: ...LearningAdvanced Features 212...
Page 356: ...344...
Page 362: ...Maintenance 350...
Page 381: ...369 TechnicalSpecification...
Page 397: ......