Table of Functions
300
Code
Comm.
Address
Name
LCD Display
Setting Range
Initial
Value
Property
*
V/F SL Ref.
selection
1 Free-Run
2 Dec
28
0h1B1C
Underload fault
time
UL Trip Time 0.0-600.0(s)
30.0
O/A
O
I/P
p.223
29
0h1B1D
Underload lower
limit level
UL LF Level 10-30(%)
30
O/A
O
I/P
p.223
30
0h1B1E
Underload
upper limit level
UL BF Level 30-100(%)
30
O/A
O
I/P
p.223
31
0h1B1F
No motor
motion at
detection
No Motor
Trip
0 None
0:None O/A
O
I/P
p.227
1 Free-Run
32
0h1B20
No motor
detection
current level
No Motor
Level
1-100(%)
5
O/A
O
I
p.227
33
0h1B21
No motor
detection delay
No Motor
Time
0.1-10.0(s)
3.0
O/A
O
I
p.227
40
0h1B28
Electronic
thermal fault
selection
ETH Trip Sel
0 None
0:None O/A
O
I/P
p.213
1 Free-Run
2 Dec
41
0h1B29
Motor cooling
fan type
Motor
Cooling
0 Self-cool
0:Self-
cool
O/A
O
I/P
p.213
1 Forced-cool
42
0h1B2A
Electronic
thermal 1
minute rating
ETH 1min
120-200(%)
150
O/A
O
I/P
p.213
43
0h1B2B
Electronic
thermal
continuous
rating
ETH Cont
50-150(%)
120
O/A
O
I/P
p.213
45
0h1B2D BX trip mode
BX Mode
0
Free-Run
0
X/A
O
I/P -
1
Dec
50
0h1B32
Stall prevention
motion and flux
braking
Stall Prevent
bit 0000-1111
0000
X/A
O
X
p.216
00
01
Acceleratin
g
001
0
At constant
speed
Summary of Contents for Rsi S Series
Page 2: ......
Page 6: ......
Page 12: ...Preparing the Installation 0...
Page 22: ...Preparing the Installation 10...
Page 70: ...LearningAdvanced Features 58...
Page 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Page 224: ...LearningAdvanced Features 212...
Page 356: ...344...
Page 362: ...Maintenance 350...
Page 381: ...369 TechnicalSpecification...
Page 397: ......