
Learning Advanced Features
166
Code
Description
KEB-1 or KEB-2 cannot be set in Cn-77.
Setting
Function
0
None
General deceleration is carried out until a low voltage
trip occurs.
1
KEB-1
When the input power is disconnected, the DC link
charges with regenerated energy from the motor.
When the input power is restored, operation changes
from the KEB operation to the frequency reference
operation. KEB Acc Time in Cn-89 is used as the
acceleration time when restoring to normal operation.
2
KEB-2
When the input power is disconnected, the DC Link
charges with regenerated energy from the motor.
When the input power is restored, operation changes
from the KEB operation to a deceleration to a stop. The
Dec Time in dr-04 is used as the deceleration time
during the deceleration to stop.
[KEB-1]
[KEB-2]
Summary of Contents for Rsi S Series
Page 2: ......
Page 6: ......
Page 12: ...Preparing the Installation 0...
Page 22: ...Preparing the Installation 10...
Page 70: ...LearningAdvanced Features 58...
Page 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Page 224: ...LearningAdvanced Features 212...
Page 356: ...344...
Page 362: ...Maintenance 350...
Page 381: ...369 TechnicalSpecification...
Page 397: ......