Installing the Inverter
30
Preinsulated Crimp Terminal Connectors (Bootlace Ferrule)
.
Use preinsulated crimp terminal connectors to increase reliability of the control terminal wiring.
Refer to the specifications below to determine the crimp terminals to fit various cable sizes.
Cable Spec.
Dimensions (inches/mm)
AWG
mm
2
L*
P
d1
D
26
0.25
10.4
0.4 /
6.0
0.04 /
1.1
0.1 /
2.5
12.4
0.5 /
8.0
22
0.50
12.0
0.45 /
6.0
0.05 /
1.3
0.125
/ 3.2
20
0.75
12.0
0.45 /
6.0
0.06 /
1.5
0.13 /
3.4
* If the length (L) of the crimp terminals exceeds 0.5” (12.7mm) after wiring, the control terminal
cover may not close fully.
To connect cables to the control terminals without using crimp terminals, refer to the following
illustration detailing the correct length of exposed conductor at the end of the control cable.
Note
•
While making wiring connections at the control terminals, ensure that the total cable length
does not exceed 165ft (50m).
•
Ensure that the length of any safety related wiring does not exceed 100ft (30m).
•
Ensure that the cable length between an LCD keypad and the inverter does not exceed 10ft
0.2”
Summary of Contents for Rsi S Series
Page 2: ......
Page 6: ......
Page 12: ...Preparing the Installation 0...
Page 22: ...Preparing the Installation 10...
Page 70: ...LearningAdvanced Features 58...
Page 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Page 224: ...LearningAdvanced Features 212...
Page 356: ...344...
Page 362: ...Maintenance 350...
Page 381: ...369 TechnicalSpecification...
Page 397: ......