Learning Advanced Features
201
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
setting
41
Multi-
function
output
monitor
DO Status
-
00– 11
bit
57
Detection
frequency
FDT
Frequency
30.00
0.00
–
Maximum
frequency
Hz
58
Detection
frequency
band
FDT Band
10.00
In
65
–
71
Px terminal
configuration
Px Define
16
Exchange
-
-
*Displayed as
on the keypad.
Multi-function Output Terminal and Relay Setting Details
Code
Description
OU.31
Relay1
Set relay (Relay 1) output options.
OU.33 Q1
Define
Select terminal (Q1) output options. Q1 is an open collector transistor output.
OU.41 DO
Status
When terminal Q1 and/or Relay1 outputs are set for frequency related functions FDT-1
through FDT-4, use parameters OU.57 FDT (Frequency), OU.58 (FDT Band) settings for
the detection criteria.
Setting
Function
0
None
No output signal.
1
FDT-1
FDT-1 setting compares the reference frequency to
the actual output (operating) frequency. Relay1 (or
Q1) closes when the difference between the two
frequencies is within ½ the FDT Band, OU.58.
Eq
: Absolute value (set frequency
–
output frequency)
< detected frequency band/2.
Ex:
When OU.58, FDT Band = 10Hz, FDT-1 functions
as shown in the graph below.
Q1
15Hz
20Hz
20Hz
40Hz
40Hz
35Hz
Frequency
reference
Operation
Frequency
Run cmd
Summary of Contents for Rsi S Series
Page 2: ......
Page 6: ......
Page 12: ...Preparing the Installation 0...
Page 22: ...Preparing the Installation 10...
Page 70: ...LearningAdvanced Features 58...
Page 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Page 224: ...LearningAdvanced Features 212...
Page 356: ...344...
Page 362: ...Maintenance 350...
Page 381: ...369 TechnicalSpecification...
Page 397: ......