Product overview
EL5101, EL5101-0010, EL5101-0011
18
Version: 4.2
3.3
Technical data
Technical data
EL5101-0000
EL5101-0010
EL5101-0011
Sensor connection
A, ¬A, B, ¬B, C, ¬C (RS422 dif-
ferential inputs)
from
hardware 09 [
}
176]
: also
single-ended connection (5 V
±20%) possible
A, ¬A, B, ¬B, C, ¬C (RS422 differential inputs)
Additional inputs
gate, latch (24 V
DC
, both max. 1 MHz permitted),
status input (max. 5 V
DC
, potential-free, switching to negative poten-
tial)
-
Sensor supply
5 V
DC
Sensor output current
0.5 A
Counter
16 bit, 16/32 bit switchable
(from
firmware 14 / hardware 09
[
}
176]
)
16 bit, 16/32 bit switchable
32 bit
Zero pulse latch
16 bit, 16/32 bit switchable
(from
firmware 14 / hardware 09
[
}
176]
)
16 bit, 16/32 bit switchable
-
Limit frequency
1 MHz
(equals 4 million increments with
4-fold evaluation)
5 MHz
(equals 20 million increments with 4-fold evaluation)
Quadrature decoder
4-fold evaluation
Distributed Clocks
in enhanced operating mode
(from
firmware 14 / hardware 09
[
}
176]
)
yes
Broken wire detection to sen-
sor
in enhanced operating mode
(from
firmware 14 / hardware 09
[
}
176]
)
yes
Commands
read, set, enable
read, set
Oversampling factor
-
n = 1..100, adjustable
Cycle time
min. 100 µs
min. 500 µs
Conversion time
-
10 µs / 100 kSps
Current consumption via E-
bus
typ. 130 mA
Current consumption from the
power contacts
0.1 A (excluding sensor load current)
Electrical isolation
500 V (E-bus/field voltage)
Bit width in process image
up to 6 bytes outputs, 22 bytes inputs, depends on parameterization
Configuration
via TwinCAT
System Manager [
}
98]
Weight
approx. 100 g
Permissible ambient tempera-
ture range during operation
-25 °C ... +60 °C (extended temperature range)
Permissible ambient tempera-
ture range during storage
-40 °C ... +85 °C
Permissible relative humidity
95%, no condensation
Dimensions (W x H x D)
approx. 27 mm x 100 mm x 70 mm (width aligned: 24 mm)
Mounting [
}
34]
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27,
see also
installation instructions [
}
36]
for enhanced mechanical load capacity
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE
ATEX [
}
45]
cULus [
}
43]
3.4
Start
For commissioning:
• mount the EL5101 as described in the chapter
Mounting and wiring [
}
34]