Product overview
EL5101, EL5101-0010, EL5101-0011
17
Version: 4.2
Fig. 11: Level interface
In differential mode only the voltage difference is evaluated, so that common-mode interference on the
transmission link does not lead to corruption of the wanted signal, since any interference affects both cables
simultaneously.
If the EL5101 is only operated in single-ended mode, a nominal level voltage between 3.5 V and 5.5 V is
expected.
The EL5101-0010 and EL5101-0011 do not support single-ended mode.
In the EL5101-0010 and EL5101-0011 versions, open circuit detection (Index 0x80n0:0B, 0x80n0:0C,
0x880n0:0C) is typically activated in the range -0.475 V > Vid > +0.475 V. For the EL5101, it is typically
activated for the range -1.5 V > Vid > +1.5 V (subject to change).
Summary of Contents for EL5101
Page 2: ......