34-2
9424200996
Motor Reporting
BE1-11
m
𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝐴𝐴𝐴𝐴𝐴𝐴
𝑈𝑈𝑈𝑈𝑈𝑈𝐴𝐴𝑉𝑉𝐴𝐴𝑈𝑈𝑒𝑒𝐴𝐴
=
𝑚𝑚𝐴𝐴𝑚𝑚
�𝑉𝑉
𝑎𝑎𝑎𝑎𝑎𝑎
𝑝𝑝ℎ𝑎𝑎𝑎𝑎𝑎𝑎
− 𝑉𝑉
𝑎𝑎𝑎𝑎𝑎𝑎
�
𝑉𝑉
𝑎𝑎𝑎𝑎𝑎𝑎
× 100%
Equation 34-2. Voltage Unbalance
Start Records
The BE1-11
m
records information about motor starts and creates motor start records. A maximum of five
motor start records are stored in nonvolatile memory. When a new motor start record is generated, the
BE1-11
m
discards the oldest of the five records and replaces it with a new one. Each motor start record is
assigned a sequential number by the BE1-11
m
.
Viewing and Downloading Motor Start Records through BESTCOMS
Plus
®
To view motor start records using BESTCOMS
Plus
, use the Metering Explorer to open the Reports, Motor
Start Records screen shown in Figure 34-3. This screen shows a list of records along with number date,
time, duration, successful start (true or false), and emergency start (true or false) for each record.
A motor start is considered successful (true) when the motor status changes from starting to running. A
motor start is considered unsuccessful (false) when the motor status changes from starting to stopped.
From this screen, you can choose to View All or View New motor start records. Click to highlight a record
and the details are displayed in the right pane. In Figure 34-3, record 007 is highlighted.
The Download button opens the download window allowing you to download and save the file associated
with the selected record. The Refresh button refreshes the list of motor start records on the screen that
are available to view/download. The Reset button resets new motor start records.
Figure 34-3. Motor Start Records Screen
Motor Start Record Items
A motor start record collects several items of information that can aid in troubleshooting without having to
sort through all of the detailed information available. The following items are contained in a typical motor
start record.
•
Station ID, Device ID, and User ID - These lines report station, device, and user information as
defined by BESTCOMSPlus.
•
Motor Start Time - This line reports the time and date of the initial trigger of the event. This is
based on the starting of the motor.
•
Motor Start Number - This line reports the sequential number assigned to the record by the
BE1-11
m
.
•
Start Duration - These lines report the time from motor start to running.
•
Max Current - This line reports the maximum of the phase currents during the motor start.
Summary of Contents for BE1-11m
Page 8: ...vi 9424200996 Revision History BE1 11m...
Page 12: ...x 9424200996 Contents BE1 11m...
Page 21: ...9424200996 1 9 BE1 11m Introduction Figure 1 1 Style Chart...
Page 22: ...1 10 9424200996 Introduction BE1 11m...
Page 40: ...3 6 9424200996 Controls and Indicators BE1 11m Figure 3 3 Front Panel Display Setup Screen...
Page 54: ...5 6 9424200996 Phase Undervoltage 27P Protection BE1 11m...
Page 56: ...6 2 9424200996 Negative Sequence Voltage 47 Protection BE1 11m...
Page 61: ...9424200996 7 5 BE1 11m Phase Overvoltage 59P Protection Figure 7 3 Overvoltage Settings Screen...
Page 62: ...7 6 9424200996 Phase Overvoltage 59P Protection BE1 11m...
Page 68: ...8 6 9424200996 Auxiliary Overvoltage 59X Protection BE1 11m...
Page 80: ...12 4 9424200996 Instantaneous Overcurrent 50 Protection BE1 11m...
Page 84: ...13 4 9424200996 Breaker Failure 50BF Protection BE1 11m...
Page 92: ...14 8 9424200996 Inverse Overcurrent 51 Protection BE1 11m...
Page 105: ...9424200996 18 3 BE1 11m Power Factor 55 Protection Figure 18 2 Power Factor Settings Screen...
Page 106: ...18 4 9424200996 Power Factor 55 Protection BE1 11m...
Page 110: ...19 4 9424200996 Resistance Temperature Detector 49RTD Protection BE1 11m...
Page 118: ...20 8 9424200996 Thermal Curve 49TC Protection BE1 11m...
Page 122: ...22 2 9424200996 Starts per Time Interval 66 Protection BE1 11m...
Page 124: ...23 2 9424200996 Restart Inhibit Protection BE1 11m...
Page 140: ...28 4 9424200996 Breaker Control Switch 101 BE1 11m...
Page 148: ...29 8 9424200996 Setting Groups BE1 11m...
Page 156: ...30 8 9424200996 Metering BE1 11m Figure 30 11 RTD Meter Screen...
Page 158: ...31 2 9424200996 Digital Points BE1 11m Figure 31 2 Digital Points Monitor Screen...
Page 177: ...9424200996 34 5 BE1 11m Motor Reporting Figure 34 9 Learned Motor Data Screen...
Page 178: ...34 6 9424200996 Motor Reporting BE1 11m...
Page 184: ...35 6 9424200996 Alarms BE1 11m...
Page 186: ...36 2 9424200996 Differential Reporting BE1 11m...
Page 196: ...38 4 9424200996 Demands BE1 11m...
Page 198: ...39 2 9424200996 Load Profile BE1 11m...
Page 208: ...41 6 9424200996 Trip Circuit Monitor 52TCM BE1 11m...
Page 212: ...42 4 9424200996 Fuse Loss 60FL BE1 11m...
Page 218: ...43 6 9424200996 BESTnet Plus BE1 11m Figure 43 8 Power Quality Page...
Page 221: ...9424200996 44 3 BE1 11m Mounting Figure 44 3 Case Side Dimensions...
Page 235: ...9424200996 45 5 BE1 11m Terminals and Connectors Figure 45 7 Example of Reversed CT Polarity...
Page 236: ...45 6 9424200996 Terminals and Connectors BE1 11m...
Page 269: ...9424200996 48 15 BE1 11m BESTlogic Plus Figure 48 4 Logic Page 1 for Default Logic...
Page 288: ...49 10 9424200996 Communication BE1 11m Figure 49 14 Modbus Mapping Screen...
Page 306: ...52 4 9424200996 Device Information BE1 11m...
Page 314: ...53 8 9424200996 Configuration BE1 11m Figure 53 3 Display Units Screen...
Page 318: ...54 4 9424200996 Introduction to Testing BE1 11m...
Page 330: ...56 6 9424200996 Commissioning Testing BE1 11m...
Page 336: ...58 4 9424200996 Phase Undervoltage 27P Test BE1 11m...
Page 340: ...59 4 9424200996 Phase Overvoltage 59P Test BE1 11m...
Page 352: ...60 12 9424200996 Auxiliary Overvoltage 59X Test BE1 11m...
Page 360: ...61 8 9424200996 Frequency 81 Test BE1 11m...
Page 364: ...62 4 9424200996 Instantaneous Undercurrent 37 Test BE1 11m...
Page 376: ...63 12 9424200996 Instantaneous Overcurrent 50 Test BE1 11m...
Page 396: ...65 16 9424200996 Inverse Overcurrent 51 Test BE1 11m...
Page 408: ...67 6 9424200996 Power 32 Test BE1 11m...
Page 412: ...68 4 9424200996 Loss of Excitation Reverse Var Based 40Q Test BE1 11m...
Page 426: ...70 10 9424200996 Thermal Curve 49TC Test BE1 11m...
Page 432: ...72 4 9424200996 Starts per Time Interval 66 Test BE1 11m...
Page 436: ...73 4 9424200996 Restart Inhibit Test BE1 11m...
Page 440: ...74 4 9424200996 Virtual Control Switches 43 Test BE1 11m...
Page 450: ...75 10 9424200996 Logic Timers 62 Test BE1 11m...
Page 464: ...79 8 9424200996 Troubleshooting BE1 11m...
Page 480: ...80 16 9424200996 Specifications BE1 11m...
Page 600: ...84 56 9424200996 Settings Calculation Examples BE1 11m Figure 84 70 Logic Page 4 Part 1...
Page 602: ...84 58 9424200996 Settings Calculation Examples BE1 11m...
Page 608: ...85 6 9424200996 BESTCOMSPlus Settings Loader Tool BE1 11m...
Page 609: ......