70-4
9424200996
Thermal Curve (49TC) Test
BE1-11
m
capacity (0 - 100%) can be monitored at Metering, Motor, Motor Meter on the front-panel
display. Verify that there is a 49TC target on the front-panel display at Metering > Status >
Targets.
Step 8: Remove three-phase current and wait until thermal capacity falls to 0% before proceeding.
(Note: The thermal capacity is forced to 0% if the 49TC element is disabled and re-enabled.)
Verify that OUT5 (Stopped) closes. Reset all targets.
Step 9: Use BESTCOMS
Plus
to open the Thermal Curve (49TC) settings screen. Set the Hot Safe Stall
Time to 1,300 seconds and set the Cold Safe Stall Time to 1,500 seconds. An equivalent
current of 1.8 A is used for the steady state thermal capacity test.
The Steady State Thermal Capacity (TCU) is calculated in Equation 70-4.
𝑇𝑇𝑇𝑇𝑇𝑇
𝑒𝑒𝑒𝑒𝑒𝑒
=
�
𝐼𝐼
𝑒𝑒𝑒𝑒
𝐼𝐼
𝑡𝑡𝑡𝑡𝑡𝑡
�
×
�
1
−
ℎ𝑠𝑠𝑡𝑡
𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠
𝑠𝑠𝑡𝑡𝑠𝑠𝑙𝑙𝑙𝑙
𝑡𝑡𝑡𝑡𝑡𝑡𝑠𝑠
𝑠𝑠𝑠𝑠𝑙𝑙𝑠𝑠
𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠
𝑠𝑠𝑡𝑡𝑠𝑠𝑙𝑙𝑙𝑙
𝑡𝑡𝑡𝑡𝑡𝑡𝑠𝑠�
=
�
1.8
2
�
×
�
1
−
1300
1500
�
= 0.12 × 100 = 12%
𝑇𝑇𝑇𝑇𝑇𝑇
Equation 70-4. Steady State Thermal Capacity
Where:
I
eq
= Equivalent Thermal Current
I
tpu
= Overload Pickup Current
Step 10: Apply 10 Aac three-phase current for five seconds (simulate motor starting). Step three-phase
current down to 1.8 Aac (simulate motor running). Navigate to Metering > Motor > Motor Meter
on the front-panel display and wait until the Thermal Capacity is 12% per Equation 70-4.
Step 11: Step the three-phase current up to 10 Aac (simulate motor starting). Verify that OUT2
(Overloaded) closes indicating an overloaded condition. Measure and record the time from
when current is raised to 10 Aac until OUT1 (Tripped) closes and the thermal capacity reaches
100%. The expected timing is 31.87 seconds (88% of 36.22 seconds because %TC starts at
12%). Reference Equation 70-3. The thermal capacity (12 to 100%) can be monitored at
Metering > Motor > Motor Meter on the front-panel display. Verify that there is a 49TC target on
the front-panel display at Metering > Status > Targets.
Step 12: Remove three-phase current and wait until thermal capacity falls to 0% before proceeding.
Verify that OUT5 (Stopped) closes. Reset all targets.
Step 13: Use BESTCOMS
Plus
to open the Thermal Curve (49TC) settings screen. Set the Max
Emergency Thermal Capacity to 200%.
Step 14: Momentarily close IN1 to enable an emergency start. An emergency start expires after one
minute if current is not applied. OUT3 toggles when Input 1 is closed. Apply 10 Aac three-phase
current (simulate motor starting). Verify that OUT2 (Overloaded) closes indicating an
overloaded condition. Verify that OUT4 (Starting) closes. Measure and record the time from
when current is applied until OUT1 (Tripped) closes and the thermal capacity reaches 200%.
The expected timing is 72.44 seconds per Equation 70-3 multiplied by 2 since the 49TC is set to
trip at 200% thermal capacity. The thermal capacity (0 to 200%) can be monitored at Metering >
Motor > Motor Meter on the front-panel display. Verify that there is a 49TC target on the front-
panel display at Metering > Status > Targets.
Step 15: Remove three-phase current and wait until thermal capacity falls to 0% before proceeding.
(Note: The thermal capacity is forced to 0% if the 49TC element is disabled and re-enabled.)
Verify that OUT5 (Stopped) closes. Reset all targets.
RTD Biasing (Optional)
If the RTD Biasing test will not be performed, skip to User Curve (Step 25).
Step 16: Use BESTCOMS
Plus
to send the operational settings in Table 70-2 to the BE1-11
m
. Reset all
targets.
Summary of Contents for BE1-11m
Page 8: ...vi 9424200996 Revision History BE1 11m...
Page 12: ...x 9424200996 Contents BE1 11m...
Page 21: ...9424200996 1 9 BE1 11m Introduction Figure 1 1 Style Chart...
Page 22: ...1 10 9424200996 Introduction BE1 11m...
Page 40: ...3 6 9424200996 Controls and Indicators BE1 11m Figure 3 3 Front Panel Display Setup Screen...
Page 54: ...5 6 9424200996 Phase Undervoltage 27P Protection BE1 11m...
Page 56: ...6 2 9424200996 Negative Sequence Voltage 47 Protection BE1 11m...
Page 61: ...9424200996 7 5 BE1 11m Phase Overvoltage 59P Protection Figure 7 3 Overvoltage Settings Screen...
Page 62: ...7 6 9424200996 Phase Overvoltage 59P Protection BE1 11m...
Page 68: ...8 6 9424200996 Auxiliary Overvoltage 59X Protection BE1 11m...
Page 80: ...12 4 9424200996 Instantaneous Overcurrent 50 Protection BE1 11m...
Page 84: ...13 4 9424200996 Breaker Failure 50BF Protection BE1 11m...
Page 92: ...14 8 9424200996 Inverse Overcurrent 51 Protection BE1 11m...
Page 105: ...9424200996 18 3 BE1 11m Power Factor 55 Protection Figure 18 2 Power Factor Settings Screen...
Page 106: ...18 4 9424200996 Power Factor 55 Protection BE1 11m...
Page 110: ...19 4 9424200996 Resistance Temperature Detector 49RTD Protection BE1 11m...
Page 118: ...20 8 9424200996 Thermal Curve 49TC Protection BE1 11m...
Page 122: ...22 2 9424200996 Starts per Time Interval 66 Protection BE1 11m...
Page 124: ...23 2 9424200996 Restart Inhibit Protection BE1 11m...
Page 140: ...28 4 9424200996 Breaker Control Switch 101 BE1 11m...
Page 148: ...29 8 9424200996 Setting Groups BE1 11m...
Page 156: ...30 8 9424200996 Metering BE1 11m Figure 30 11 RTD Meter Screen...
Page 158: ...31 2 9424200996 Digital Points BE1 11m Figure 31 2 Digital Points Monitor Screen...
Page 177: ...9424200996 34 5 BE1 11m Motor Reporting Figure 34 9 Learned Motor Data Screen...
Page 178: ...34 6 9424200996 Motor Reporting BE1 11m...
Page 184: ...35 6 9424200996 Alarms BE1 11m...
Page 186: ...36 2 9424200996 Differential Reporting BE1 11m...
Page 196: ...38 4 9424200996 Demands BE1 11m...
Page 198: ...39 2 9424200996 Load Profile BE1 11m...
Page 208: ...41 6 9424200996 Trip Circuit Monitor 52TCM BE1 11m...
Page 212: ...42 4 9424200996 Fuse Loss 60FL BE1 11m...
Page 218: ...43 6 9424200996 BESTnet Plus BE1 11m Figure 43 8 Power Quality Page...
Page 221: ...9424200996 44 3 BE1 11m Mounting Figure 44 3 Case Side Dimensions...
Page 235: ...9424200996 45 5 BE1 11m Terminals and Connectors Figure 45 7 Example of Reversed CT Polarity...
Page 236: ...45 6 9424200996 Terminals and Connectors BE1 11m...
Page 269: ...9424200996 48 15 BE1 11m BESTlogic Plus Figure 48 4 Logic Page 1 for Default Logic...
Page 288: ...49 10 9424200996 Communication BE1 11m Figure 49 14 Modbus Mapping Screen...
Page 306: ...52 4 9424200996 Device Information BE1 11m...
Page 314: ...53 8 9424200996 Configuration BE1 11m Figure 53 3 Display Units Screen...
Page 318: ...54 4 9424200996 Introduction to Testing BE1 11m...
Page 330: ...56 6 9424200996 Commissioning Testing BE1 11m...
Page 336: ...58 4 9424200996 Phase Undervoltage 27P Test BE1 11m...
Page 340: ...59 4 9424200996 Phase Overvoltage 59P Test BE1 11m...
Page 352: ...60 12 9424200996 Auxiliary Overvoltage 59X Test BE1 11m...
Page 360: ...61 8 9424200996 Frequency 81 Test BE1 11m...
Page 364: ...62 4 9424200996 Instantaneous Undercurrent 37 Test BE1 11m...
Page 376: ...63 12 9424200996 Instantaneous Overcurrent 50 Test BE1 11m...
Page 396: ...65 16 9424200996 Inverse Overcurrent 51 Test BE1 11m...
Page 408: ...67 6 9424200996 Power 32 Test BE1 11m...
Page 412: ...68 4 9424200996 Loss of Excitation Reverse Var Based 40Q Test BE1 11m...
Page 426: ...70 10 9424200996 Thermal Curve 49TC Test BE1 11m...
Page 432: ...72 4 9424200996 Starts per Time Interval 66 Test BE1 11m...
Page 436: ...73 4 9424200996 Restart Inhibit Test BE1 11m...
Page 440: ...74 4 9424200996 Virtual Control Switches 43 Test BE1 11m...
Page 450: ...75 10 9424200996 Logic Timers 62 Test BE1 11m...
Page 464: ...79 8 9424200996 Troubleshooting BE1 11m...
Page 480: ...80 16 9424200996 Specifications BE1 11m...
Page 600: ...84 56 9424200996 Settings Calculation Examples BE1 11m Figure 84 70 Logic Page 4 Part 1...
Page 602: ...84 58 9424200996 Settings Calculation Examples BE1 11m...
Page 608: ...85 6 9424200996 BESTCOMSPlus Settings Loader Tool BE1 11m...
Page 609: ......