13-2
9424200996
Breaker Failure (50BF) Protection
BE1-11
m
ReTrip and Trip
The adjustable delay timer allows time for current to clear or the breaker status to transition after signaling
the breaker to trip. The delay timer is initiated when either the 52BFI input or the 50BFI input becomes
true. When both signals are false, the breaker delay timer
is stopped.
ReTrip
The ReTrip output is true when the delay timer is actively timing. The delay timer can be stopped by
several methods depending on the timer initiate source. When initiated by a 50BFI signal, the timer is
stopped when current decreases below the pickup setting, when the fast current dropout detector detects
that current has dropped out, or when the control timer expires. When initiated by a 52BFI signal, the
timer is stopped when the BRKSTAT logic element indicates that the breaker is open. Regardless of
initiate method, asserting the Block logic input also stops the timer. In BESTlogic
Plus
, the ReTrip output
can be connected to other logic elements to annunciate the condition, control other elements in logic, and
start the fault recorder (logic element FAULTTRIG).
Trip
The Trip output becomes true when the delay timer expires. In BESTlogic
Plus
, the Trip output can be
connected to other logic elements and to a physical relay output to annunciate the condition and to initiate
corrective action. If a target is enabled for the element, the BE1-11
m
will record a target when the Trip
output becomes true. See the
Fault Reporting
chapter for more information about target reporting.
Fast Current Detector
The fast current detector directly determines when the current in the poles of the breaker has been
interrupted without having to wait for the fault current samples to clear the one-cycle filter time used by
the normal current measurement function. This function has less than one cycle dropout time.
The fast current detector logic is true if the current has been interrupted and is used to stop the breaker
failure timer. The I=0 algorithm looks at the sample data directly and does not rely upon the 1 cycle
phasor estimation calculation. It rejects dc tail-off by looking for the characteristic exponential decay.
Current is deemed to be interrupted when the current in all three phases is below 5% nominal or if the
current is decaying exponentially. Only the three phase currents are monitored by this function.
CT Source
The CT Source setting configures the breaker failure element to monitor CT circuit 1 or CT circuit 2 on
protection systems equipped with two sets of CTs. CT circuit 1 terminals are designated D1 (IA1) through
D8 (IG1) and CT circuit 2 terminals are designated F1 (IA2) through F8 (IG2). For an illustration, refer to
the
Terminals and Connectors
chapter.
Programmable Alarm
A Breaker Failure alarm is provided to indicate an alarm condition when the 50BF element trips. The
alarm appears on the front-panel display, web page interface, and on the Alarms metering screen in
BESTCOMS
Plus
. Refer to the
Alarms
chapter for information on how to program alarms.
Element Blocking
The Block input provides logic-supervision control of the element. Element blocking is a useful feature to
prevent inadvertent backup tripping during testing.
When true, the Block input disables the element by forcing the Trip and ReTrip outputs to logic 0 and
resetting the element timers. Connect the element Block input to the desired logic in BESTlogic
Plus
.
When the element is initially selected from the Elements view, the default condition of the Block input is a
logic 0.
Summary of Contents for BE1-11m
Page 8: ...vi 9424200996 Revision History BE1 11m...
Page 12: ...x 9424200996 Contents BE1 11m...
Page 21: ...9424200996 1 9 BE1 11m Introduction Figure 1 1 Style Chart...
Page 22: ...1 10 9424200996 Introduction BE1 11m...
Page 40: ...3 6 9424200996 Controls and Indicators BE1 11m Figure 3 3 Front Panel Display Setup Screen...
Page 54: ...5 6 9424200996 Phase Undervoltage 27P Protection BE1 11m...
Page 56: ...6 2 9424200996 Negative Sequence Voltage 47 Protection BE1 11m...
Page 61: ...9424200996 7 5 BE1 11m Phase Overvoltage 59P Protection Figure 7 3 Overvoltage Settings Screen...
Page 62: ...7 6 9424200996 Phase Overvoltage 59P Protection BE1 11m...
Page 68: ...8 6 9424200996 Auxiliary Overvoltage 59X Protection BE1 11m...
Page 80: ...12 4 9424200996 Instantaneous Overcurrent 50 Protection BE1 11m...
Page 84: ...13 4 9424200996 Breaker Failure 50BF Protection BE1 11m...
Page 92: ...14 8 9424200996 Inverse Overcurrent 51 Protection BE1 11m...
Page 105: ...9424200996 18 3 BE1 11m Power Factor 55 Protection Figure 18 2 Power Factor Settings Screen...
Page 106: ...18 4 9424200996 Power Factor 55 Protection BE1 11m...
Page 110: ...19 4 9424200996 Resistance Temperature Detector 49RTD Protection BE1 11m...
Page 118: ...20 8 9424200996 Thermal Curve 49TC Protection BE1 11m...
Page 122: ...22 2 9424200996 Starts per Time Interval 66 Protection BE1 11m...
Page 124: ...23 2 9424200996 Restart Inhibit Protection BE1 11m...
Page 140: ...28 4 9424200996 Breaker Control Switch 101 BE1 11m...
Page 148: ...29 8 9424200996 Setting Groups BE1 11m...
Page 156: ...30 8 9424200996 Metering BE1 11m Figure 30 11 RTD Meter Screen...
Page 158: ...31 2 9424200996 Digital Points BE1 11m Figure 31 2 Digital Points Monitor Screen...
Page 177: ...9424200996 34 5 BE1 11m Motor Reporting Figure 34 9 Learned Motor Data Screen...
Page 178: ...34 6 9424200996 Motor Reporting BE1 11m...
Page 184: ...35 6 9424200996 Alarms BE1 11m...
Page 186: ...36 2 9424200996 Differential Reporting BE1 11m...
Page 196: ...38 4 9424200996 Demands BE1 11m...
Page 198: ...39 2 9424200996 Load Profile BE1 11m...
Page 208: ...41 6 9424200996 Trip Circuit Monitor 52TCM BE1 11m...
Page 212: ...42 4 9424200996 Fuse Loss 60FL BE1 11m...
Page 218: ...43 6 9424200996 BESTnet Plus BE1 11m Figure 43 8 Power Quality Page...
Page 221: ...9424200996 44 3 BE1 11m Mounting Figure 44 3 Case Side Dimensions...
Page 235: ...9424200996 45 5 BE1 11m Terminals and Connectors Figure 45 7 Example of Reversed CT Polarity...
Page 236: ...45 6 9424200996 Terminals and Connectors BE1 11m...
Page 269: ...9424200996 48 15 BE1 11m BESTlogic Plus Figure 48 4 Logic Page 1 for Default Logic...
Page 288: ...49 10 9424200996 Communication BE1 11m Figure 49 14 Modbus Mapping Screen...
Page 306: ...52 4 9424200996 Device Information BE1 11m...
Page 314: ...53 8 9424200996 Configuration BE1 11m Figure 53 3 Display Units Screen...
Page 318: ...54 4 9424200996 Introduction to Testing BE1 11m...
Page 330: ...56 6 9424200996 Commissioning Testing BE1 11m...
Page 336: ...58 4 9424200996 Phase Undervoltage 27P Test BE1 11m...
Page 340: ...59 4 9424200996 Phase Overvoltage 59P Test BE1 11m...
Page 352: ...60 12 9424200996 Auxiliary Overvoltage 59X Test BE1 11m...
Page 360: ...61 8 9424200996 Frequency 81 Test BE1 11m...
Page 364: ...62 4 9424200996 Instantaneous Undercurrent 37 Test BE1 11m...
Page 376: ...63 12 9424200996 Instantaneous Overcurrent 50 Test BE1 11m...
Page 396: ...65 16 9424200996 Inverse Overcurrent 51 Test BE1 11m...
Page 408: ...67 6 9424200996 Power 32 Test BE1 11m...
Page 412: ...68 4 9424200996 Loss of Excitation Reverse Var Based 40Q Test BE1 11m...
Page 426: ...70 10 9424200996 Thermal Curve 49TC Test BE1 11m...
Page 432: ...72 4 9424200996 Starts per Time Interval 66 Test BE1 11m...
Page 436: ...73 4 9424200996 Restart Inhibit Test BE1 11m...
Page 440: ...74 4 9424200996 Virtual Control Switches 43 Test BE1 11m...
Page 450: ...75 10 9424200996 Logic Timers 62 Test BE1 11m...
Page 464: ...79 8 9424200996 Troubleshooting BE1 11m...
Page 480: ...80 16 9424200996 Specifications BE1 11m...
Page 600: ...84 56 9424200996 Settings Calculation Examples BE1 11m Figure 84 70 Logic Page 4 Part 1...
Page 602: ...84 58 9424200996 Settings Calculation Examples BE1 11m...
Page 608: ...85 6 9424200996 BESTCOMSPlus Settings Loader Tool BE1 11m...
Page 609: ......