9424200996
16-1
BE1-11
m
Power (32) Protection
16 • Power (32) Protection
The power (32) element monitors three-phase real power (watts). The element can be configured to
protect against overpower or underpower conditions.
Element logic connections are made on the BESTlogic
™
Plus
screen in BESTCOMS
Plus
®
and element
operational settings are configured on the Power settings screen in BESTCOMS
Plus
. A summary of the
logic inputs and outputs and operational settings appears at the end of this chapter.
Note
BE1-11
m
protection systems enabled for IEC-61850 communication
(style Mxxxx5xxxxxxxx) have their power protection element fixed at
one underpower element.
BESTCOMS
Plus
Navigation Path:
Settings Explorer, Protection, Power, Power (32)
HMI Navigation Path:
Settings Explorer, Protection, Settings Group x (where x = 0 to 3), Power
Protection, Power 32
Element Operation
Power protection can be used in applications where excessive power flow in the tripping direction is
undesirable. Directional power protection is desirable in applications where:
•
Reduced power can indicate a loss of load on the motor.
•
Power flows into the secondary of a station distribution transformer, indicating an industrial or
private customer is supplying power into the utility system.
•
Excessive load has been connected to a system.
•
Overload has been placed on a distribution system.
•
Overspeeding is a prime concern.
•
An open breaker creates an overload on a local generation facility.
Mode
Four modes of protection are available. One of Three mode activates protection when the power on one
of the three phases exceeds the Pickup setting. Two of Three mode activates protection when the power
on any two of the three phases exceeds the Pickup setting. Three of Three mode activates protection
when the power on all three phases exceeds the Pickup setting. Total Power mode activates protection
when the total power exceeds the Pickup setting. The element remains in the picked-up condition until
power flow falls below the dropout ratio of 95% of the actual pickup.
To clarify the difference between Three of Three and Total Power modes, assume that Two of Three
mode has been selected and the pickup setting is 30 watts. Therefore, the BE1-11
m
picks up when two of
the three phases have exceeded 30 watts. Alternately, if two phases are zero (0) watts and the third
phase is 70 watts, the BE1-11
m
does not pickup because two of the phases have not exceeded the
pickup threshold required for operation in Two of Three mode. Any two phases must exceed the pickup
threshold for operation to occur. However, if the 32 element was set for Total Power mode, the same
power values previously mentioned would result in a pickup condition because “Total Power” (0 + 0 + 70
watts) exceeds the three-phase pickup setting of 30 watts. For details on power calculations, refer to the
Configuration
chapter.
Bus CT Configuration
On protection systems equipped with two sets of CTs, the power element can monitor CT circuit 1 or CT
circuit 2. The CT source is selected on the Sensing Transformers settings screen in BESTCOMS
Plus
.
Summary of Contents for BE1-11m
Page 8: ...vi 9424200996 Revision History BE1 11m...
Page 12: ...x 9424200996 Contents BE1 11m...
Page 21: ...9424200996 1 9 BE1 11m Introduction Figure 1 1 Style Chart...
Page 22: ...1 10 9424200996 Introduction BE1 11m...
Page 40: ...3 6 9424200996 Controls and Indicators BE1 11m Figure 3 3 Front Panel Display Setup Screen...
Page 54: ...5 6 9424200996 Phase Undervoltage 27P Protection BE1 11m...
Page 56: ...6 2 9424200996 Negative Sequence Voltage 47 Protection BE1 11m...
Page 61: ...9424200996 7 5 BE1 11m Phase Overvoltage 59P Protection Figure 7 3 Overvoltage Settings Screen...
Page 62: ...7 6 9424200996 Phase Overvoltage 59P Protection BE1 11m...
Page 68: ...8 6 9424200996 Auxiliary Overvoltage 59X Protection BE1 11m...
Page 80: ...12 4 9424200996 Instantaneous Overcurrent 50 Protection BE1 11m...
Page 84: ...13 4 9424200996 Breaker Failure 50BF Protection BE1 11m...
Page 92: ...14 8 9424200996 Inverse Overcurrent 51 Protection BE1 11m...
Page 105: ...9424200996 18 3 BE1 11m Power Factor 55 Protection Figure 18 2 Power Factor Settings Screen...
Page 106: ...18 4 9424200996 Power Factor 55 Protection BE1 11m...
Page 110: ...19 4 9424200996 Resistance Temperature Detector 49RTD Protection BE1 11m...
Page 118: ...20 8 9424200996 Thermal Curve 49TC Protection BE1 11m...
Page 122: ...22 2 9424200996 Starts per Time Interval 66 Protection BE1 11m...
Page 124: ...23 2 9424200996 Restart Inhibit Protection BE1 11m...
Page 140: ...28 4 9424200996 Breaker Control Switch 101 BE1 11m...
Page 148: ...29 8 9424200996 Setting Groups BE1 11m...
Page 156: ...30 8 9424200996 Metering BE1 11m Figure 30 11 RTD Meter Screen...
Page 158: ...31 2 9424200996 Digital Points BE1 11m Figure 31 2 Digital Points Monitor Screen...
Page 177: ...9424200996 34 5 BE1 11m Motor Reporting Figure 34 9 Learned Motor Data Screen...
Page 178: ...34 6 9424200996 Motor Reporting BE1 11m...
Page 184: ...35 6 9424200996 Alarms BE1 11m...
Page 186: ...36 2 9424200996 Differential Reporting BE1 11m...
Page 196: ...38 4 9424200996 Demands BE1 11m...
Page 198: ...39 2 9424200996 Load Profile BE1 11m...
Page 208: ...41 6 9424200996 Trip Circuit Monitor 52TCM BE1 11m...
Page 212: ...42 4 9424200996 Fuse Loss 60FL BE1 11m...
Page 218: ...43 6 9424200996 BESTnet Plus BE1 11m Figure 43 8 Power Quality Page...
Page 221: ...9424200996 44 3 BE1 11m Mounting Figure 44 3 Case Side Dimensions...
Page 235: ...9424200996 45 5 BE1 11m Terminals and Connectors Figure 45 7 Example of Reversed CT Polarity...
Page 236: ...45 6 9424200996 Terminals and Connectors BE1 11m...
Page 269: ...9424200996 48 15 BE1 11m BESTlogic Plus Figure 48 4 Logic Page 1 for Default Logic...
Page 288: ...49 10 9424200996 Communication BE1 11m Figure 49 14 Modbus Mapping Screen...
Page 306: ...52 4 9424200996 Device Information BE1 11m...
Page 314: ...53 8 9424200996 Configuration BE1 11m Figure 53 3 Display Units Screen...
Page 318: ...54 4 9424200996 Introduction to Testing BE1 11m...
Page 330: ...56 6 9424200996 Commissioning Testing BE1 11m...
Page 336: ...58 4 9424200996 Phase Undervoltage 27P Test BE1 11m...
Page 340: ...59 4 9424200996 Phase Overvoltage 59P Test BE1 11m...
Page 352: ...60 12 9424200996 Auxiliary Overvoltage 59X Test BE1 11m...
Page 360: ...61 8 9424200996 Frequency 81 Test BE1 11m...
Page 364: ...62 4 9424200996 Instantaneous Undercurrent 37 Test BE1 11m...
Page 376: ...63 12 9424200996 Instantaneous Overcurrent 50 Test BE1 11m...
Page 396: ...65 16 9424200996 Inverse Overcurrent 51 Test BE1 11m...
Page 408: ...67 6 9424200996 Power 32 Test BE1 11m...
Page 412: ...68 4 9424200996 Loss of Excitation Reverse Var Based 40Q Test BE1 11m...
Page 426: ...70 10 9424200996 Thermal Curve 49TC Test BE1 11m...
Page 432: ...72 4 9424200996 Starts per Time Interval 66 Test BE1 11m...
Page 436: ...73 4 9424200996 Restart Inhibit Test BE1 11m...
Page 440: ...74 4 9424200996 Virtual Control Switches 43 Test BE1 11m...
Page 450: ...75 10 9424200996 Logic Timers 62 Test BE1 11m...
Page 464: ...79 8 9424200996 Troubleshooting BE1 11m...
Page 480: ...80 16 9424200996 Specifications BE1 11m...
Page 600: ...84 56 9424200996 Settings Calculation Examples BE1 11m Figure 84 70 Logic Page 4 Part 1...
Page 602: ...84 58 9424200996 Settings Calculation Examples BE1 11m...
Page 608: ...85 6 9424200996 BESTCOMSPlus Settings Loader Tool BE1 11m...
Page 609: ......