Maintenance
Azbil Corporation
3-22
Model SLX 110/120 - Smart displacement type level transmitter
Saving calibrated values and canceling constant current source mode
Use the following procedure to forcibly write the calibrated values into the non-
volatile memory of this instrument and cancel the constant current source mode.
Step
Button
Procedure
SFC screen
1
SHIFT
Press [SHIFT].
SHIFT- #
2
ENTER
( Yes )
NON-VOL
Press [ENTER].
- Forced data writing is completed.
SLX TAG NO.
WORKING...
i
SLX TAG - 0001
DATA NONVOLATILE #
SLX TAG - 0001
READY...
3
OUT- J
PUT
INPUT
Press [OUTPUT].
The current output is 100%.
SLX TAG - 0001
WORKING...
i
OUTPUT TAG - 0001
100 % #
4
CLR
( No )
Press [CLR].
- The “#” disappears, indicating that
the constant current source mode has
been cancelled.
SLX TAG - 0001
WORKING...
i
SLX TAG - 0001
READY...