Operation
Azbil Corporation
2-38
Model SLX 110/120 - Smart displacement type level transmitter
However, since the upper range value at this time becomes 330 mm (the span remains
unchanged at 300 mm), it is necessary to reset set the upper range value to 300 mm
(the span is therefore changed to 270 mm).
Actual level input
This input should be done while the liquid level is 0% equivalent.
Step
Button
Procedure
SFC screen
1
LRV E
0%
Press [LRV]. The current lower range
value will appear.
LRV TAG - 0001
0.1200 mm
2
G
SET
Press [SET].
LRV TAG - 0001
SET LRV ?
3
ENTER
( Yes )
NON-VOL
Press [ENTER].
LRV TAG - 0001
WORKING...
4
The actual input level becomes the zero
point. Setting completed.
LRV TAG - 0001
-0.0800 mm
Zero adjustment that adjusts to the actual level (pinpoint adjustment)
Normal zero adjustment is performed by entering 0% while the liquid level is 0%
equivalent.
Step
Button
Procedure
SFC screen
1
OUT- J
PUT
INPUT
Press [OUTPUT].
OUTPUT TAG-0001
WORKING...
2
The current output value will appear.
OUTPUT TAG - 0001
0.00 %
3
Enter the desired output using numeric
keys.
Example: Enter value of 55
OUTPUT TAG-0001
55_ %
Summary of Contents for SLX 110
Page 1: ...Smart Displacement type Level Transmitter Model SLX 110 120 User s Manual CM2 SLX100 2001...
Page 4: ......
Page 8: ...iv Model SLX 110 120 Smart displacement type level transmitter...
Page 120: ...Operation Azbil Corporation 2 80 Model SLX 110 120 Smart displacement type level transmitter...
Page 150: ...Maintenance Azbil Corporation 3 30 Model SLX 110 120 Smart displacement type level transmitter...
Page 162: ...Azbil Corporation 5 2 Model SLX 110 120 Smart displacement type level transmitter...
Page 163: ......
Page 166: ......
Page 168: ......