Repair
Azbil Corporation
4-6
Model SLX 110/120 - Smart displacement type level transmitter
• When SFC or communication system is suspected to be experiencing error
Message
Meaning
Action
SLX TAG - 0001
SFC FAULT
SFC defect
- Redo the communication
start procedure.
- If this message still appears,
contact Azbil Corporation.
SLX TAG - 0001
FAILED COMM CHK
Introductory remarks of error
message
SLX TAG-0001
ILLEGAL RESPONSE 1or2or..11
Communication defect
Check the connection between
the SFC and transmitter,
wiring and power supply.
SLX TAG - 0001
PRINTER FAIL !
Printer operation impossible
Contact Azbil Corporation.
SLX TAG - 0001
LOW LOOP RES
Insufficient loop resistance
Check the resistance value.
SLX TAG - 0001
HI RES / LOW VOLT
- Excessive loop resistance
- Insufficient applied voltage
- Check the loop resistance.
- Increase the applied voltage.
• When operational error is suspected
Message
Meaning
Action
NOT SUPORT
The key pressed is not
applicable.
Press the correct key.
EXCESSIVE OUTPUT
Required output value in
constant current source mode
> output range (-1.25% to
105%)
When inappropriate numeric
value is input by dedicated
function
Press [CLR] and redo input.
CLR
( No )
Summary of Contents for SLX 110
Page 1: ...Smart Displacement type Level Transmitter Model SLX 110 120 User s Manual CM2 SLX100 2001...
Page 4: ......
Page 8: ...iv Model SLX 110 120 Smart displacement type level transmitter...
Page 120: ...Operation Azbil Corporation 2 80 Model SLX 110 120 Smart displacement type level transmitter...
Page 150: ...Maintenance Azbil Corporation 3 30 Model SLX 110 120 Smart displacement type level transmitter...
Page 162: ...Azbil Corporation 5 2 Model SLX 110 120 Smart displacement type level transmitter...
Page 163: ......
Page 166: ......
Page 168: ......