Operation
Azbil Corporation
2-16
Model SLX 110/120 - Smart displacement type level transmitter
When adjusting zero point to output value according to real level
• The zero point is adjusted so that the current input value becomes the desired
output value (the span does not change).
• Example of use: Adjust the output to the readout of the liquid level of the glass
gauge.
Method using SFC
Step
Button
Procedure
SFC screen
1
OUT- J
PUT
INPUT
Press [OUTPUT].
OUTPUT TAG-0001
WORKING...
2
The current output value is displayed.
OUTPUT TAG-0001
40.0 %
3
Enter the desired output using numeric
keys.
Example: Enter value of 55
OUTPUT TAG-0001
55_ %
4
G
SET
Press SET.
OUTPUT TAG-0001
SET REQ. LEVEL ?
5
ENTER
( Yes )
NON-VOL
Press [ENTER].
OUTPUT TAG-0001
WORKING...
6
The zero point is changed so that the
current real input level becomes the
desired output value. Setting completed
OUTPUT TAG-0001
55.0 % ...