Maintenance
Model SLX 110/120 - Smart displacement type level transmitter 3-21
Step
Button
Procedure
SFC screen
6
COR- K
RECT
RESET
Press [CORRECT].
- Carry out step 7 if the reading is
lower than 20 mA, and carry out step 8
if the reading is higher than 20 mA.
OUTPUT TAG - 0001
CORRECT DAC SPAN
7
H
NEXT
Press [NEXT].
- Check the reading of the ammeter,
while pressing this key.
OUTPUT TAG-0001
WORKING...
OUTPUT TAG - 0001
INCREASED 20mA
OUTPUT TAG - 0001
INCREASED 4mA #
8
L
PREV
Press [PREV].
- Check the reading of the ammeter,
while pressing this key.
OUTPUT TAG-0001
WORKING...
i
OUTPUT TAG - 0001
DECREASED 20mA
OUTPUT TAG - 0001
DECREASED 4mA #
9
CLR
( No )
When calibration is completed, press
[CLR].
SLX TAG - 0001
READY...
10
- Save the calibrated values according
to 4 and exit the constant current
source mode.