Operation
Azbil Corporation
2-6
Model SLX 110/120 - Smart displacement type level transmitter
Checking set data
SFC connections
•
Connect the SFC as shown in the figure below.
• Be sure to connect the SFC communication cable and terminals of this instrument
as follows.
Red wire: terminal
Black wire: Supply - terminal
CHK
-/
S-
S
+
CHK
+/M -
E
M +
DISP FLOW UP ZERO DOWN
%
(S+ Terminal)
SUPPLY-
(CHK- / S- Terminal)
Load resistance
more than250 Ohms
Supply voltage
24V DC
Ground
Black
Communication cable
Red
SFC
-
+
Control signal
4-20mA
External ground
Figure 2-6 Connection with SFC